1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 176
Input
The module enables the following parameters to be measured
Input
Measurement
Range
Resolution
Accuracy
(1)
PT1000
Temperature
-50 .. 250 °C
0.01 °C
± 0.25 °C
(2)
4-20mA current loop
DC current
0 .. 100 %
(3)
0.1 %
± 0.5 %
(4)
NOTES:
(1) accuracy refers to the 3T module without sensors; for complete accuracy, consider the
characteristics of the sensors and cabling used
(2) accurate within the range -25 ..
2
50 °C; in the complete range it is: ± 0.5°C
(3) the measurement is expressed as a percentage, in which: 0 % = 4 mA and 100 % = 20 mA
(4) accuracy refers to the full scale: 0.5 %= 0.1 mA
Interface
Five signalling LEDs are available:
Figure 45
LED
Description
Power
Reports ON status and correct communication with trip unit:
off: module off
fixed or flashing light synchronized with power LED of Ekip Touch: module ON and
communication with Trip unit present
flashing not synchronized with power LED of Ekip Touch (two rapid flashes per
second): module ON and communication with Trip unit absent
I 41, I 42,
I 43, I 44
Indicate status of the input contacts:
off: input disabled
fixed on: input enabled, sensor connected and measurement valid
flashing: input enabled, sensor not connected and/or measurement not valid
Access from
display
If the
Ekip Signalling 3T
module is detected correctly, the following areas became available on
the trip unit:
Measurements
page, accessible from
Home
(see page xx), containing the
measurements of all the PT1000 inputs and 4-20mA current loops of both 3T-1 and 3T-
2 modules
information submenu in the
Modules-Information
menu containing: serial number,
module version and sensors status (Present/Alarm)
IMPORTANT:
if one or more sensors are in alarm status, this signal is activated on
the diagnosis bar: Ekip Signalling 3T
if a sensor is not enables, the reported state is: Present
Remote
configurations
The module configuration is available:
via Ekip Connect, with communication accessories from service connector or with
communication from system bus
with its own communication system and Ekip Com modules fitted to the circuit-breaker
in the conditions prescribed for the trip unit (use the System Interface for the details)
In both the conditions, also all the measurements, statuses and alarms of the module are
available.
NOTE: parameters and measurements are distributed on
Ekip Connect
pages and
communication addresses that are sometimes not consequential; the following tables
show the page references to
Ekip Connect 2
Содержание SACE Tmax XT2
Страница 82: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 82 L curve IEC 60255 151 SI L curve IEC 60255 151 VI ...
Страница 83: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 83 L curve IEC 60255 151 EI L curve t k I4 ...
Страница 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Страница 85: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 85 S curve t k Curve S2 I curve MCR curve 2I curve ...
Страница 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Страница 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Страница 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Страница 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Страница 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Страница 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Страница 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Страница 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Страница 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Страница 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...
Страница 207: ...1SDH002031A1002 ECN000092998 Rev B ...