Configurations
on menu
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the
Settings menu
(page 114).
If the module is detected correctly by Ekip Touch, in the Settings Modules menu, the following
communication parameters can be configured:
Parameter
Description
Default
Static IP address
ON
Defines whether the module has the dynamic IP
address (Off) or static IP address (On)
If = On all associated parameters are enabled
Off
Static IP address
Enables the static IP to be selected
0.0.0.0
Static Network
Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway
address
In the presence of several subnets it enables the IP
address to be selected of the node to which the module
is connected
0.0.0.0
SNTP client
enabled
Permits enabling of SNTP distribution protocol of the
clock and synchronization signal
OFF
SNTP address
Server
Enables the network server to be set that supplies
SNTP
0.0.0.0
Information on
menu
If the module is detected correctly by Ekip Touch in the
About
-
Modules
menu the following
information is available:
Information
Description
SN and version
Identification and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the
moment of the connection to the network in the event of configuration
with dynamic IP or can be set by menu in the case of a static IP
NOTE: without a DHCP server, the module automatically
adopts a causal IP address in the interval 169.254.xxx.xxx
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients
Gateway
address
IP address of the node to which the module is connected, in the presence
of several subnets
MAC Address
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an Ethernet
device
Cfg file
Name of the configuration file loaded in the modules
Error Cfg file
Error code of the configuration file (0 = no error)
Содержание SACE Tmax XT2
Страница 82: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 82 L curve IEC 60255 151 SI L curve IEC 60255 151 VI ...
Страница 83: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 83 L curve IEC 60255 151 EI L curve t k I4 ...
Страница 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Страница 85: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 85 S curve t k Curve S2 I curve MCR curve 2I curve ...
Страница 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Страница 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Страница 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Страница 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Страница 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Страница 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Страница 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Страница 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Страница 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Страница 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...
Страница 207: ...1SDH002031A1002 ECN000092998 Rev B ...