Communication
71
Table 9.Parameter mapping
Register addresses, which are not allocated to any drive
parameter or data set, are invalid. Attempting to read from or write
to such an address will make the Modbus/TCP interface return an
exception code to the controller.
Refer to the drive manuals for drive-specific information such as
the data sets supported, and parameter numbers. Data set
registers are updated in a cyclic interval. Updating of parameter
registers happens at a slower interval.
Parameter
4
GGPP
GG
PP
Data sets
Each data set consists
of 3 data words. For
example, ‘Data word
2.3’ refers to the 3rd
word in data set 2.
4
0001
…4
0096
00
Data sets
01
Data word 1.1
02
Data word 1.2
03
Data word 1.3
04
Data word 2.1
05
Data word 2.2
06
Data word 2.3
07
Data word 3.1
…
94
Data word 32.1
95
Data word 32.2
96
Data word 32.3
Parameters
4
0101
…4
0199
01
Group 01
01
Index 01
02
Index 02
…
99
Index 99
4
0201
…4
0299
02
Group 02
01
Index 01
02
Index 02
…
99
Index 99
…
…
…
4
9901
…4
9999
99
Group 99
01
Index 01
02
Index 02
…
99
Index 99
Содержание RETA-02
Страница 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 10: ...Table of contents 10 ...
Страница 14: ...Introduction 14 ...
Страница 30: ...Mechanical installation 30 ...
Страница 32: ...Electrical installation 32 ...
Страница 42: ...Drive configuration 42 ...
Страница 48: ...Network configuration 48 ...
Страница 50: ...Master configuration 50 ...
Страница 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Страница 68: ...Communication profiles 68 ...
Страница 106: ...Diagnostics 106 ...
Страница 111: ......