Communication profiles
57
Table 6. The Status Word for the PROFIdrive communication
profile. The upper case boldface text refers to the states shown in
Figure 11.
Bit Name
Value
STATE/Description
0
RDY_ON
1
READY TO SWITCH ON
.
0
NOT READY TO SWITCH ON
.
1
RDY_RUN
1
READY TO OPERATE
.
0
OFF1 ACTIVE
.
2
RDY_REF
1
ENABLE OPERATION
.
0
DISABLE OPERATION
.
3
TRIPPED
1
FAULT
.
0
No fault.
4
OFF_2_STA
1
OFF2 inactive.
0
OFF2 ACTIVE
.
5
OFF_3_STA
1
OFF3 inactive.
0
OFF3 ACTIVE
.
6
SWC_ON_INHIB
1
SWITCH-ON INHIBIT ACTIVE
.
0
SWITCH-ON INHIBIT NOT ACTIVE
.
7
ALARM
1
Warning/Alarm.
0
No Warning/Alarm.
8
AT_SETPOINT
1
OPERATING.
Actual value equals reference value
(i.e. is within tolerance limits).
0
Actual value differs from reference value
(= is outside tolerance limits).
9
REMOTE
1
Drive control location: REMOTE.
0
Drive control location: LOCAL.
10 ABOVE_LIMIT
1
Actual frequency or speed value equals or is greater
than supervision limit.
0
Actual frequency or speed value is within supervision
limit.
Содержание RETA-02
Страница 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 02 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 10: ...Table of contents 10 ...
Страница 14: ...Introduction 14 ...
Страница 30: ...Mechanical installation 30 ...
Страница 32: ...Electrical installation 32 ...
Страница 42: ...Drive configuration 42 ...
Страница 48: ...Network configuration 48 ...
Страница 50: ...Master configuration 50 ...
Страница 58: ...Communication profiles 58 11 to 15 Drive specific Bit Name Value STATE Description ...
Страница 68: ...Communication profiles 68 ...
Страница 106: ...Diagnostics 106 ...
Страница 111: ......