1.
Confirm that
OperationPAR
is set to
CC
for each transformer in the parallel
group.
2.
Confirm that
OperCCBlock
is set to
On
for each transformer in the parallel
group.
3.
Review the setting for
CircCurrLimit
.
4.
Review the setting for
CircCurrBk
to confirm whether a circulating current
limit will result in an
Alarm
state,
Auto Block
or
Auto&Man Block
of the
automatic voltage control for tap changer, for parallel control function
TR8ATCC.
5.
Inject a voltage UB equal to
USet
for each transformer.
6.
Inject a load current for Transformer 1 that is equal to rated load current
IBase
(for winding 2, which is defined in a global base function, selected with
setting
GlobalBaseSel2
for TR8ATCC) and a load current for Transformer 2
that is 1% less than (
IBase
– (
IBase
· CircCurrLimit))
7.
Confirm that the automatic voltage control for tap changer, for parallel
control function TR8ATCC responds in accordance with the setting for
CircCurrBk
. Alarm and blocking conditions can be confirmed through
interrogation of the event menu or the control menu on the local HMI.
VTmismatch during parallel operation
1.
Confirm that
OperationPAR
is set to
MF
for each transformer in the parallel
group.
2.
Review the setting for
VTmismatch
and
tVTmismatch
.
3.
Inject a voltage UB equal to
USet
for Transformer 1 and a voltage less than
(
USet
– (
VTmismatch
·
USet
)) for Transformer 2.
4.
This condition should result in a
VTmismatch
which will mutually block the
operation of the automatic voltage control for tap changer, parallel control
function TR8ATCC for all transformers connected in the parallel group,
which can be confirmed through interrogation of the local HMI.
5.
Confirm that the automatic voltage control for tap changer, parallel control
function TR8ATCC responds in accordance with the setting for
CircCurrBk
.
6.7.1.8
Completing the test
Continue to test another function or end the testing by setting the parameter
TestMode
to
Off
under
Main menu/Tests/IED test mode/1:TESTMODE
. If
another function is tested, then set the parameter
Blocked
to
No
under
Main menu/
Tests/Function test modes/Control/TR8ATCC(90)/X:TR8ATCC
for the
function, or for each individual function in a chain, to be tested next. Remember to
set the parameter
Blocked
to
Yes
, for each individual function that has been tested.
Section 6
1MRK 504 126-UEN -
Testing functionality
74
Commissioning Manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Commissioning Manual...
Страница 2: ......
Страница 8: ......
Страница 14: ...6...
Страница 20: ...12...
Страница 26: ...18...
Страница 38: ...30...
Страница 46: ...38...
Страница 86: ...78...
Страница 108: ...100...
Страница 109: ...101...