IEC18000085-1-en.vsdx
IEC18000085 V1 EN-US
Figure 43: Read through fault confirmation window
In order to open the TFM tool successfully in PCM600, the configuration
between the PCM600 tool and the IED should match. If the configuration is not
same between the PCM600 tool and the IED, then read configuration from IED
via Read from IED option in PCM600 need to be performed.
A warning message dialog box appears, if the through fault monitoring
function is not configured in the IED.
Deleting through fault reports from the IED
GUID-FAAA98A3-E5E7-4A01-BA1E-BF8C35C86CCA v1
In order to delete through fault reports from the IED via PCM600 at function block instance
level, proceed as follows:
1.
Select the function block instance from the Through fault monitoring function selection
.
IEC18000086-1-en.vsdx
IEC18000086 V1 EN-US
Figure 44: Select function block instance
2.
Select the IED menu and click on Clear through fault reports option as shown in
IEC18000087-1-en.vsdx
IEC18000087 V1 EN-US
Figure 45: Clear through fault reports
A confirmation dialog box appears.
Section 7
1MRK 500 127-UEN D
Operating procedures
60
670 series
Operation manual