Section 7
Operating procedures
7.1
Monitoring
7.1.1
Indications
GUID-E3CC6AB4-D6C4-4504-A0F2-CA76EA3D7FCD v10
The operation of the IED can be monitored via three different indications on the LHMI.
•
Three indicator LEDs with fixed functionality: Ready, Start and Trip
•
15 programmable three-color alarm LEDs which can present 45 virtual LED states
•
For each on state LED color and for the LED off state, texts can be programmed with
PCM600 and via LHMI. These texts are displayed on the LHMI.
•
An auto-indicating message on the display.
7.1.1.1
Using auto-indication messages
AMU0600430 v9
Auto-indication messages are shown in a dialog box that is displayed when the disturbance
recorder is triggered. The indication dialog box shows a list of current disturbance recordings
one by one. To scroll the dialog, use
and
.
To activate the auto-indication message function, the disturbance recorder
function has to be activated and properly configured. Check also that the
setting Main menu/Configuration/HMI/Screen/SCREEN:1/AutoIndicationDRP
is set to
On.
1.
Read the auto-indication message in the dialog box.
The message contains the same information that is available for disturbance recordings.
2.
Press
to see more detailed information.
3.
Press
to close the auto-indication message without clearing it or press
to activate
the Clear view and to clear messages.
1MRK 500 127-UEN D
Section 7
Operating procedures
670 series
51
Operation manual