7.5.2
Importing ICD or CID files
GUID-D8A6D372-7E16-4004-AAF6-F6E3BAC64E30 v1
Procedure to import a complete ICD file or CID file:
1.
Select an existing IED to import IEC 61850 files.
2.
Select the file type of IEC 61850 to import from the
Files of type drop down list (ICD or
CID)
3.
The
SCL Import Option menu opens, which queries how the file should be handled during
import, see
3.1. Ignore
Substation Section will not import the "SSD-file" part of the SCD-file.
3.2.
Don't import ... protects the existing IEDs in case the SCD file does not match the
original configuration in PCM600.
3.3.
Replace unknown ... can be used when it is known that the file includes additional
IEDs which are needed. The IED of type
Generic IEC 61850 IED is used to integrate
these kinds of IEDs in for example the plant structure.
3.4. Click
Ignore PCM Object Type to update the IED object(s) in PCM600 from the IED
type(s) in the SCD file, disregarding if the IED type(s) in the SCD file matches the IED
object(s) in PM600 or not.
3.5. Start
Import when the definition has been completed. A progress window presents
the import procedure.
4.
Section 7