IEC08000271.vsd

Execution order

group 1

Execution order

group 2

Execution order

group 3

Execution Flow

IEC08000271 V1 EN-US

Figure 36: ACT: Concept of Execution order sequence

In the conceptual MainApplication example in 

Figure 36

, the execution order of the main

function block in the execution order group 2 defines the execution orders needed in group 1

and 3. The preceding logic done with function blocks in group 1 must have a lower execution

order than the ones in group 2. The following function blocks in group 3 must have a higher

execution order than the main function block in group 2.

5.1.5 

Configuration parameters

GUID-52044790-0A7C-4D83-8634-887593A903BC v4

Configuration parameters are found in the parameter setting tool. For example, the SMAI

function block has to be configured to support AC-current values or AC-voltage values.

5.1.6 

Connections and variables

GUID-1564FB6D-2682-49AE-A1D5-8B7F03E4204B v3

A connection is the link or "wire" between function block outputs and inputs.

Rules and methods to do connections:

Drag a line between two signals.

Link two signals by using variables.

It is possible to search and replace variable names in ACT.

Connection validation

A connection is only useful and possible between two signals of the same data type, see 

Figure

37

.

Section 5

1MRK 511 284-UEN B

Protection and control engineering

46

650 series

Engineering manual

© Copyright 2013 ABB. All rights reserved

Содержание RELION 650 SERIES

Страница 1: ...Relion 650 SERIES 650 series Version 1 3 IEC Engineering manual...

Страница 2: ......

Страница 3: ...Document ID 1MRK 511 284 UEN Issued November 2019 Revision B Product version 1 3 Copyright 2013 ABB All rights reserved...

Страница 4: ...L Project for use in the OpenSSL Toolkit http www openssl org This product includes cryptographic software written developed by Eric Young eay cryptsoft com and Tim Hudson tjh cryptsoft com Trademarks...

Страница 5: ...roduct failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipme...

Страница 6: ...rning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN...

Страница 7: ...al key 19 4 4 Setting up communication between PCM600 and the IED 22 4 5 Project managing in PCM600 27 4 6 Building a plant structure 28 4 6 1 IEC 61850 naming conventions to identify an IED 29 4 7 In...

Страница 8: ...ting SCL files from PCM600 79 7 3 1 Exporting SCD files 79 7 3 2 Exporting ICD or CID files 80 7 4 Engineering of vertical and horizontal communication in IET600 81 7 5 Importing SCL files to PCM600 8...

Страница 9: ...ed audience GUID C9B8127F 5748 4BEA 9E4F CC762FE28A3A v9 This manual addresses system and project engineers involved in the engineering process of a project and installation and commissioning personne...

Страница 10: ...nical and electrical installation The chapters are organized in the chronological order in which the IED should be installed The commissioning manual contains instructions on how to commission the IED...

Страница 11: ...E D853043AB731 v5 1 1 1 1 1 3 3 Related documents GUID DEA16B32 29D9 40B2 BC9F 12F3AEA90245 v7 650 series manuals Identity number Communication protocol manual DNP 3 0 1MRK 511 280 UEN Communication p...

Страница 12: ...are shown in Courier font For example to save the changes in non volatile memory select Yes and press Parameter names are shown in italics For example the function can be enabled and disabled with the...

Страница 13: ...ction zero negative sequence direction SDEPSDE 67N Sensitive directional residual overcurrent and power protection UC2PTUC 37 Time delayed two step undercurrent protection LCPTTR 26 Thermal overload p...

Страница 14: ...ntrol 8 signals AUTOBITS AutomationBits command function for DNP3 0 I103CMD Function commands for IEC 60870 5 103 I103IEDCMD IED commands for IEC 60870 5 103 I103USRCMD Function commands user defined...

Страница 15: ...TMAGGIO Trip matrix logic OR Configurable logic blocks OR INVERTER Configurable logic blocks inverter PULSETIMER Configurable logic blocks PULSETIMER GATE Configurable logic blocks controllable gate...

Страница 16: ...IO IEC 61850 generic communication I O functions SP16GGIO IEC 61850 generic communication I O functions 16 inputs MVGGIO IEC 61850 generic communication I O functions MVEXP Measured value expander blo...

Страница 17: ...functions IEC 61850 or Function name Function description Basic functions included in all products INTERRSIG Self supervision with internal event list ACTVGRP Parameter setting groups TESTMODE Test mo...

Страница 18: ...12...

Страница 19: ...neering and configuration PCM600 is used to do the complete engineering and configuration activities needed for bay level IEDs Product type and version specific engineering data needed by PCM600 for p...

Страница 20: ...e applications can be organized in IED product engineering IED communication engineering per protocol IED system monitoring IED product diagnostic This manual is valid for PCM600 supporting the 650 se...

Страница 21: ...ding files with the assistance of the Disturbance Handling tool Creating overview reports of recording file content for fast evaluation with assistance of the Disturbance Handling tool Service managem...

Страница 22: ...ng allowed activities for the user profiles to use the read and write function Once the engineering of the IED is done the results must be written to the IED Conversely some parts of the engineering i...

Страница 23: ...Save the work between the different steps Project Create plant structure Write configuration to IED IEC61850 Supported protocols IEC 61850 configuration tool IEC08000122 V3 EN US Figure 4 IED engineer...

Страница 24: ...ups GDE Single line diagram configuration Create a single line diagram Include measurements when needed Link the dynamic elements to functions created in ACT for example a breaker object to the switch...

Страница 25: ...all 650 series IEDs The IED specific module is separate for each type of IED Installing IED Connectivity package The Connectivity package is available on the CD that was distributed along with the IED...

Страница 26: ...d update it to PCM600 or write the PCM600 technical key to the IED The user can also define an own technical key The error message displayed due to mismatch between PCM600 and IED technical key is sho...

Страница 27: ...0380 1 en vsd IEC09000380 V1 EN US Figure 7 PCM600 Technical key editor Using the Technical Key Editor the following selections are possible use the existing technical key in the IED use the existing...

Страница 28: ...th cases 1 If needed set the IP address for the IEDs 2 Set up the PC or workstation for a direct link point to point or 3 Connect the PC or workstation to the LAN WAN network 4 Configure the IED IP ad...

Страница 29: ...nals from the IED are received on the Tx pin on the PC Thus a straight standard Ethernet cable can be used When a PC is connected to the IED and the setting DHCPServer is set to On via the local HMI p...

Страница 30: ...Figure 9 Select Search programs and files 2 Type View network connections and click on the View network connections icon Section 4 1MRK 511 284 UEN B Setting up a project 24 650 series Engineering man...

Страница 31: ...1 en vsd IEC13000059 V1 EN US Figure 11 Right click Local Area Connection and select Properties 4 Select the TCP IPv4 protocol from the list of configured components using this connection and click Pr...

Страница 32: ...S Figure 13 Select Obtain an IP address automatically 6 Select Use the following IP address and define IP address and Subnet mask if the front port is used and if the IP address is not set to be obtai...

Страница 33: ...Open existing projects Import projects Create new projects Export projects Delete projects Rename projects Copy and paste projects Migrate projects from one product version to another It is possible t...

Страница 34: ...image of the substation and the bays within the substation The organization structure for the IEDs may differ from the structure of the primary equipment in the substation In PCM600 it is possible to...

Страница 35: ...section is only valid when the IEC 61850 standard is used for station bus communication According to the IEC 61850 6 clause 8 4 the SCL model allows two kinds of project designation in the object pro...

Страница 36: ...level voltage level bay level and IED level using the Object properties window as shown in Figure 17 The station level has been renamed as DMSTAT The voltage level has been renamed as C1 The bay leve...

Страница 37: ...e done without any synchronization with the IED The offline configuration in PCM600 can be synchronized with the physical IED at a later state by connecting the IED to PCM600 Import a template IED ava...

Страница 38: ...000662 V1 EN US Figure 20 PCM600 Communication port and IP address 6 Cross check that the IED whose IP address has been inserted has been detected online by PCM600 see Figure The user can not scan dat...

Страница 39: ...ay type of the IED see Figure 22 IEC09000682 1 en vsd IEC09000682 V1 EN US Figure 22 PCM600 IED housing and display type detection 9 The Setup Complete Page dialog shows the summary of the IED Type IE...

Страница 40: ...ne mode has an advantage compared to online mode that one can start preparing configuration even though IED is not available Setting up an IED in offline mode is almost similar to that of an online mo...

Страница 41: ...IEC09000665 V4 EN US Figure 24 PCM600 IED Version selection 1MRK 511 284 UEN B Section 4 Setting up a project 650 series 35 Engineering manual Copyright 2013 ABB All rights reserved...

Страница 42: ...d In hardware tool it is possible to change the hardware configuration of the IED after it is inserted for example if wrong selections were made in off line mode when no license file was used Section...

Страница 43: ...lant structure Change the IP address the name and the technical key that corresponds to the physical IED after a template IED has been imported A template IED can only be inserted when the bay is sele...

Страница 44: ...emplate click Import Template to import a template from the selection window or click Create to insert the selected IED to the bay see Figure 27 It is possible to insert more than one IED from the Cre...

Страница 45: ...ED Ordered default configurations are not locked The user can use any of the available default configurations for a particular product type as a base to create an own configuration The only requiremen...

Страница 46: ...US Figure 31 Alternative 2 IP address via IED Object Properties window Procedure 1 Select the IED to enter the IP address 2 Open the Object Properties window 3 Place the cursor in the IP address row...

Страница 47: ...mapped as logical nodes for example Logical gates Timers The basic general features of the Application configuration tool ACT Organization of an application configuration Organize an application conf...

Страница 48: ...ed names for function blocks and signals marked with blue text Signals that have a user defined name created in ACT will only be visible in PST if the IED configuration is written to the IED and read...

Страница 49: ...as set of input and output signals A function block can contain more signals than needed in that application part A signal that is not used in a particular application is possible to hide in the funct...

Страница 50: ...s parameters from the drop down lists in ACT In automatic mode best suitable instance is selected automatically Depending on the function block type not all three parameters are selectable The cycle t...

Страница 51: ...ization The application execution within the 650 series products is organized in three time classes see Figure 34 IEC09000739 V1 EN US Figure 34 ACT Possible MainApplication cycle times For the same t...

Страница 52: ...ration parameters GUID 52044790 0A7C 4D83 8634 887593A903BC v4 Configuration parameters are found in the parameter setting tool For example the SMAI function block has to be configured to support AC c...

Страница 53: ...nection is also represented in SMT with a cross mark Hardware channels are always visible in SMT Supported hardware channels are Binary input channels Binary output channels Analog input channels A ha...

Страница 54: ...cation configuration Validation is made when creating the application configuration for example A connection between two input signals or two output signals is not possible A connection between two di...

Страница 55: ...ainApplication Page Area where the problems are identified IEC09000614_2_en vsd IEC09000614 V2 EN US Figure 39 ACT Validation on demand Validation when writing to the IED When writing the application...

Страница 56: ...the IED at runtime Setting group Nearly all settings used by the IED for the protection application functions are organized in a group of settings Up to four setting groups can be configured with dif...

Страница 57: ...output channel can only be activated from one function block output If it should be activated from more than one function block output glue logic has to be used Glue logic means inserting a logical g...

Страница 58: ...signals Depending on the IED capability SMT has a separate sheet for each possible combination The possible sheets are Binary Inputs Binary Outputs Analog Inputs GOOSE Receive Section 5 1MRK 511 284...

Страница 59: ...function keys and LEDs on LHMI it is needed to insert the corresponding special function blocks for these operation element groups The function blocks for the LEDs are organized as single function blo...

Страница 60: ...ion Configuration tool Figure describes the basic LHMI and the operation element groups These are the 15 LEDs and their belonging text elements on the LCD A They are operated by the keys a and b The o...

Страница 61: ...rators command when the key is pressed as output signal The functions are activated whenever a key is pressed the first time The corresponding text elements for the five keys appear on the left side o...

Страница 62: ...he status of the signal The LED illuminates flashing F LatchedAck F S The LED latches the signal change OFF ON and flashes F until it is acknowledged When the signal is still ON at the time the signal...

Страница 63: ...tool and Parameter Setting tool Six operation modes are listed in the drop down menu in Parameter Setting tool Follow S Follow F LatchedAck F S LatchedAck S F LatchedColl S LatchedReset S LED operatio...

Страница 64: ...Flash Illumination IEC08000397 V1 EN US Figure 48 LHMI LED operation mode LatchedAck F S Base The classical mode to indicate incoming alarms or warnings which the operator has not seen since the last...

Страница 65: ...re signals with higher priority are changing to ON after an acknowledgement The higher priority color signal will illuminate in flash mode See Figure 49 and Figure 50 for these two principles IEC08000...

Страница 66: ...Illumination Man Reset S1 S2 S3 S4 tMax tRestart S1LED S2LED S3LED S4LED Auto Reset IEC08000400 V1 EN US Figure 52 LHMI LED operation mode LatchedReset S This mode is useful to monitor signals that ar...

Страница 67: ...US Figure 53 LHMI LED operation mode LatchedReset S 2 6 2 Single line diagram engineering GUID 4EF97104 327A 443F AA00 7C4BF143D46D v2 Phase angles are shown as radians in the single line diagram GDE...

Страница 68: ...that is presented as a single line diagram on this HMI page Rules to handle HMI pages Several single line diagrams can be created for one bay The IED supports one bay The sequence order of the HMI pa...

Страница 69: ...of variables A set of three symbols are either valid to present a double point information or to present an integer value position out of 32 binary outputs The corresponding function blocks in ACT ar...

Страница 70: ...n a selection box placed in the upper area above the page A line that is not connected to a symbol may be done in any line width in the range 1 5 But it needs to be simple connection points to be draw...

Страница 71: ...onnections Junction 1 Connections Busbar junction 2 Connections Earth 10 Connections Feeder end 21 Measuring transformers Current transformer 5 Measuring transformers Voltage transf 2 windings 6 Table...

Страница 72: ...SSCBR SSIML SSIMG CNTGGIO STBRREC HZPDIF GENPDIF TR8ATCC T2WPDIF T3WPDIF MVGGIO SPVNZBAT SESRSYN LCPTTR LFPTTR LMBRFLO OEXPVPH L4UFCNT SXSWI CVMMXN TEIGGIO SXCBR ETPMMTR Others Capacitor 7 Others Sur...

Страница 73: ...Isolator 11 Undefined Switchgear Breaker 00 Middle position 4 SCSWI Breaker 01 Open Breaker 10 Closed Breaker 11 Undefined Switchgear Truck 00 Middle position 22 SXSWI SXCBR Truck 01 Open Truck 10 Cl...

Страница 74: ...perated 10 Closed Isolator motor operated 11 Undefined Switchgear Isolator2 00 Middle position 32 SCSWI Isolator2 01 Open Isolator2 10 Closed Isolator2 11 Undefined Switchgear Isolator2 indication onl...

Страница 75: ...t button 00 Middle position 30 VSGGIO Select button 01 Open Select button 10 Closed Select button 11 Undefined Texts Indication button 00 Middle position 31 VSGGIO Indication button 01 Open Indication...

Страница 76: ...lete HMI display page Procedure 1 Make a sketch how to present the single line diagram 2 Place the apparatus transformer and other symbols that are needed for the single line diagram into the raster b...

Страница 77: ...iver the needed information Switch controller of type CSWI for an apparatus All configured function blocks with measurements of type MMXU for the measurements VSGGIO for one bit indications for the dy...

Страница 78: ...S Figure 59 GDE Object properties windows for text insertion The single line diagram screen can display different values with the help of the dynamic text fields Please remember that these values are...

Страница 79: ...ts and indications GUID B895D621 07EF 4788 863D 19C361C66917 v3 To get IED events to the LHMI event list and indications for Ready Start and Trip indication LEDs disturbance report needs to be enginee...

Страница 80: ...74...

Страница 81: ...here is a strict relation between the function blocks and the logical node types This relation is automatically handled by the PCM600 tools The concept in IED is such that the 61850 data for each func...

Страница 82: ...enever a function block is instantiated in ACT PCM600 automatically generates the corresponding logical node data In Figure 61 this is shown by two parts per function block The upper part is the visib...

Страница 83: ...o a GOOSE receive function block GOOSEBINRCV GOOSEINTLKRCV GOOSESPRCV GOOSEDPRCV GOOSEINTRCV or GOOSEMVRCV in SMT If the quality of the value is needed in the receiver IED the quality must be included...

Страница 84: ...ered 7 2 2 Sequence for engineering of IEC 61850 protocol SEMOD58549 17 v6 The IEC 61850 standard defines the complete part needed for information communication in a substation This can be split into...

Страница 85: ...ll IEDs in the project must be engineered in PCM600 The hardware interface for example the communication port has to be selected and configured The used interface addresses have to be set according to...

Страница 86: ...e plant structure 1 Right click the IED in the plant structure and select Export to open the Export window 2 Select the type of file to export from the Save as type drop down list Configured IED Descr...

Страница 87: ...fault data sets The 650 series configured IED includes a number of predefined data sets but it is possible to add additional data sets and or reconfigure default data sets according to the requirement...

Страница 88: ...engineering 7 5 Importing SCL files to PCM600 GUID DA35857B 999B 4533 8148 864B69ECDBCE v1 The IED engineering tool must be able to receive a SCD file or an ICD file as import to receive the engineer...

Страница 89: ...he current project 4 5 Start Import when the file definition has been completed A progress window presents the import procedure 5 Make connections from sending IEDs to receiving function blocks in SMT...

Страница 90: ...existing IEDs in case the SCD file does not match the original configuration in PCM600 3 3 Replace unknown can be used when it is known that the file includes additional IEDs which are needed The IED...

Страница 91: ...ion of functions that represent a logical node When a changed configuration is written to the IED the user is asked to update the communication configuration 1 Select Yes in the Update Communication w...

Страница 92: ...86...

Страница 93: ...unicated from either of these serial interfaces The user must select in PST which interface to use 8 1 1 Operation selection for RS485 and optical serial communication M17109 118 v7 Both COM03 and COM...

Страница 94: ...to 9600 bits s or 19200 bits s RevPolarity Setting for inverting the light or not Standard IEC 60870 5 103 setting is On CycMeasRepTime Setting for CycMeasRepTime must be coordinated with the xDbRepIn...

Страница 95: ...t the signal configuration to project definitions The signal type can not be modified due to the fact that the internal signal set up is fixed When the default configuration values are sufficient the...

Страница 96: ...ting group the user defined names are used 2 Open the Communication Management Tool CMT Set the Signal Type to Binary Input Object and choose the connection of the master for which the values should b...

Страница 97: ...ls and move them into the DNP signal list of the master DNP point zero and one of the Binary Input Objects are used for indicating the active setting group in this case 1MRK 511 284 UEN B Section 9 DN...

Страница 98: ...project configuration in PCM600 to make all signals visible for CMT Direct configured hardware channels in the application configuration see Figure 76 appear in CMT see Figure 77 Do not configure thes...

Страница 99: ...new window and click OK Figure 78 presents the design of the two container windows which open after the selection of DNP3 The right window shows tabs for possible communication channels The left wind...

Страница 100: ...selection Content changes in the DNP3 container are marked with a star at the end of the name see Figure 80 The star indicates that changes in the container have to be saved before leaving CMT IEC080...

Страница 101: ...e window and get the new configuration see Figure 83 IEC08000338 vsd IEC08000338 V1 EN US Figure 83 CMT Select Class window 9 4 1 Configuring DNP3 class GUID B46924F8 B960 4B79 8EB8 4DFADABDFB10 v1 In...

Страница 102: ...485 specific parameters GUID 52662B86 51CB 48EB A67B 12699085B451 v1 There are a few parameters that are specific to RS485 and are separated from the protocols This makes it possible to run RS485 hard...

Страница 103: ...Standards CB Circuit breaker CCITT Consultative Committee for International Telegraph and Telephony A United Nations sponsored standards body within the International Telecommunications Union CCVT Ca...

Страница 104: ...nd fault protection EPA Enhanced performance architecture ESD Electrostatic discharge F SMA Type of optical fibre connector FAN Fault number FCB Flow control bit Frame count bit FOX 20 Modular 20 chan...

Страница 105: ...s IED Intelligent electronic device I GIS Intelligent gas insulated switchgear Instance When several occurrences of the same function are available in the IED they are referred to as instances of that...

Страница 106: ...PC MIP Mezzanine card standard POR Permissive overreach POTT Permissive overreach transfer trip Process bus Bus or LAN used at the process level that is in near proximity to the measured and or contro...

Страница 107: ...SD Unix TCP IP was developed by DARPA for Internet working and encompasses both network layer and transport layer protocols While TCP and IP specify two protocols at specific protocol layers TCP IP is...

Страница 108: ...tion on which UT1 is based The Coordinated Universal Time is expressed using a 24 hour clock and uses the Gregorian calendar It is used for aeroplane and ship navigation where it is also sometimes kno...

Страница 109: ...103...

Страница 110: ...AB Grid Automation Products SE 721 59 V ster s Sweden Phone 46 0 21 32 50 00 www abb com protection control Copyright 2013 ABB All rights reserved Scan this QR code to visit our website 1MRK 511 284...

Отзывы: