The data set for GOOSE may contain signals on data attribute level or on
FCDA level. The latter is also called structured GOOSE.
Ensure that the same GoID is set for sending and receiving GOOSE
messages.
Note that one data must only be included in one GOOSE data set. Data set
for GOOSE can not be empty.
7.
Create the GOOSE control block and connect it to the GOOSE message data set. Be sure
to check the parameters for the GOOSE control block and update as required.
8. Connect the GOOSE control block to the client IEDs, subscribing for GOOSE.
9. Export the updated SCD file.
Please see the IET600 user manual for additional information about vertical
and horizontal station communication engineering.
7.5
Importing SCL files to PCM600
GUID-DA35857B-999B-4533-8148-864B69ECDBCE v1
The IED engineering tool must be able to receive a SCD file or an ICD file as import to receive
the engineered communication extensions, for example for the different IEDs.
7.5.1
Importing SCD files
GUID-93604C46-1A65-4A25-9334-59478FC1C0A0 v5
Procedure to import a SCD file to PCM600:
1.
Select the station in the plant structure.
2.
Right-click the station and select
Import ...
3.
Select the file to be imported from the open standard Windows menu and start the
reading.
4. A
SCL Import Options window opens, which queries how the file should be handled during
import, see
.
IEC09000631-1-en.vsd
IEC09000631 V1 EN-US
Figure 68: IEC 61850: Import SCD file
Section 7
1MRK 511 284-UEN B
IEC 61850 communication engineering
82
650 series
Engineering manual