The IED is equipped with an optical Ethernet rear port for
the substation communication standard IEC 61850-8-1.
IEC 61850-8-1 protocol allows intelligent electrical devices
(IEDs) from different vendors to exchange information
and simplifies system engineering. Peer-to-peer
communication according to GOOSE is part of the
standard. Disturbance files uploading is provided.
Disturbance files are accessed using the IEC 61850-8-1
protocol. Disturbance files are available to any Ethernet
based application via FTP in the standard Comtrade
format. Further, the IED can send and receive binary
values, double point values and measured values (for
example from MMXU functions), together with their
quality, using the IEC 61850-8-1 GOOSE profile. The IED
meets the GOOSE performance requirements for tripping
applications in substations, as defined by the IEC 61850
standard. The IED interoperates with other IEC 61850-
compliant IEDs, tools, and systems and simultaneously
reports events to five different clients on the IEC 61850
station bus.
The event system has a rate limiter to reduce CPU load.
The event channel has a quota of 10 events/second. If the
quota is exceeded the event channel transmission is
blocked until the event changes is below the quota, no
event is lost.
All communication connectors, except for the front port
connector, are placed on integrated communication
modules. The IED is connected to Ethernet-based
communication systems via the fibre-optic multimode LC
connector (100BASE-FX).
The IED supports SNTP and IRIG-B time synchronization
methods with a time-stamping resolution of 1 ms.
• Ethernet based: SNTP and DNP3
• With time synchronization wiring: IRIG-B
The IED supports IEC 60870-5-103 time synchronization
methods with a time stamping resolution of 5 ms.
Table 1. Supported communication interface and protocol
alternatives
Interfaces/
Protocols
Ethernet
100BASE-FX LC
ST connector
IEC 61850-8-1
●
DNP3
●
IEC 60870-5-103
●
●
= Supported
Horizontal communication via GOOSE for interlocking
GUID-92ECE152-892C-4214-95DE-B92718689434 v2
GOOSE communication can be used for exchanging
information between IEDs via the IEC 61850-8-1 station
communication bus. This is typically used for sending
apparatus position indications for interlocking or
reservation signals for 1-of-n control. GOOSE can also be
used to exchange any boolean, integer, double point and
analog measured values between IEDs.
DNP3 protocol
GUID-54A54716-23BD-4E7C-8245-DE2B4C75E8DC v1
DNP3 (Distributed Network Protocol) is a set of
communications protocols used to communicate data
between components in process automation systems. For
a detailed description of the DNP3 protocol, see the DNP3
Communication protocol manual.
IEC 60870-5-103 communication protocol
M11874-3 v3
IEC 60870-5-103 is an unbalanced (master-slave) protocol
for coded-bit serial communication exchanging
information with a control system, and with a data
transfer rate up to 38400 bit/s. In IEC terminology, a
primary station is a master and a secondary station is a
slave. The communication is based on a point-to-point
principle. The master must have software that can
interpret IEC 60870-5-103 communication messages.
15. Hardware description
Layout and dimensions
IP14539-1 v1
Mounting alternatives
M16079-3 v6
The following mounting alternatives are available (IP40
protection from the front):
• 19” rack mounting kit
• Wall mounting kit
• Flush mounting kit
• 19" dual rack mounting kit
See ordering for details about available mounting
alternatives.
Busbar protection REB650
1MRK 505 265-BUS B
Version 1.1 ANSI
ABB Power Grids
17
© Copyright 2011 ABB Power Grids. All rights reserved