Scheme communication
Logic
IP11406-1 v1
M12380-1 v4
Table 33. Tripping logic SMPPTRC (94)
Function
Range or value
Accuracy
Trip action
3-ph
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
M11443-1 v6
Table 34. Configurable logic blocks
Logic block
Quantity with cycle time
Range or value
Accuracy
5 ms
20 ms
100 ms
AND
60
60
160
-
-
OR
60
60
160
-
-
XOR
10
10
20
-
-
INVERTER
30
30
80
-
-
SRMEMORY
10
10
20
-
-
RSMEMORY
10
10
20
-
-
GATE
10
10
20
-
-
PULSETIMER
10
10
20
(0.000–90000.000) s
± 0.5% ± 25 ms
TIMERSET
10
10
20
(0.000–90000.000) s
± 0.5% ± 25 ms
LOOPDELAY
10
10
20
Busbar protection REB650
1MRK 505 265-BUS B
Version 1.1 ANSI
34
ABB Power Grids