Table 16. Electromagnetic compatibility tests, continued
Description
Type test value
Reference
Electromagnetic emission tests
EN 55011, class A
IEC 60255-25
• Conducted, RF-emission (mains terminal)
0.15...0.50 MHz
< 79 dB(µV) quasi peak
< 66 dB(µV) average
0.5...30 MHz
< 73 dB(µV) quasi peak
< 60 dB(µV) average
• Radiated RF-emission
30...230 MHz
< 40 dB(µV/m) quasi peak, measured at 10 m
distance
230...1000 MHz
< 47 dB(µV/m) quasi peak, measured at 10 m
distance
GUID-83755DD7-E73B-442B-A0DF-87D648F7CF01 v3
Table 17. Insulation tests
Description
Type test value
Reference
Dielectric tests:
IEC 60255-5
ANSI C37.90-2005
• Test voltage
2 kV, 50 Hz, 1 min
1 kV, 50 Hz, 1 min, communication
Impulse voltage test:
IEC 60255-5
ANSI C37.90-2005
• Test voltage
5 kV, unipolar impulses, waveform 1.2/50 μs,
source energy 0.5 J
1 kV, unipolar impulses, waveform 1.2/50 μs,
source energy 0.5 J, communication
Insulation resistance measurements
IEC 60255-5
ANSI C37.90-2005
• Isolation resistance
>100 MΏ, 500 V DC
Protective bonding resistance
IEC 60255-27
• Resistance
<0.1 Ώ (60 s)
GUID-F98A61B6-B290-43E5-BDF7-96FE3300F28E v2
Table 18. Mechanical tests
Description
Reference
Requirement
Vibration response tests (sinusoidal)
IEC 60255-21-1
Class 2
Vibration endurance test
IEC60255-21-1
Class 1
Shock response test
IEC 60255-21-2
Class 1
Shock withstand test
IEC 60255-21-2
Class 1
Bump test
IEC 60255-21-2
Class 1
Seismic test
IEC 60255-21-3
Class 2
Busbar protection REB650
1MRK 505 265-BUS B
Version 1.1 ANSI
ABB Power Grids
25
© Copyright 2011 ABB Power Grids. All rights reserved