M13304-1 v5
Table 29. Two step overvoltage protection OV2PTOV (59)
Function
Range or value
Accuracy
Operate voltage, low and high step
(1-200)% of
VBase
± 0.5% of V
n
at V < V
n
± 0.5% of V at V > V
n
Reset ratio
>95%
-
Inverse time characteristics for low and high step, see table
-
See table
Definite time delay, step 1
(0.00 - 6000.00) s
± 0.5% ± 25 ms
Definite time delays, step 2
(0.000-60.000) s
± 0.5% ± 25 ms
Minimum operate time, Inverse characteristics
(0.000-60.000) s
± 0.5% ± 25 ms
Operate time, pickup function
30 ms typically at 0 to 2 x V
set
-
Reset time, pickup function
40 ms typically at 2 to 0 x V
set
-
Critical impulse time
10 ms typically at 0 to 2 x V
set
-
Impulse margin time
15 ms typically
-
M13317-2 v5
Table 30. Two step residual overvoltage protection ROV2PTOV (59N)
Function
Range or value
Accuracy
Operate voltage, step 1
(1-200)% of
VBase
± 0.5% of V
n
at V < V
n
± 0.5% of V at V > V
n
Operate voltage, step 2
(1–100)% of
VBase
± 0.5% of V
n
at V < V
n
± 0.5% of V at V > V
n
Reset ratio
>95%
-
Inverse time characteristics for low and high step, see table
-
See table
Definite time setting, step 1
(0.00–6000.00) s
± 0.5% ± 25 ms
Definite time setting, step 2
(0.000–60.000) s
± 0.5% ± 25 ms
Minimum operate time for step 1 inverse characteristic
(0.000-60.000) s
± 0.5% ± 25 ms
Operate time, pickup function
30 ms typically at 0 to 2 x V
set
-
Reset time, pickup function
40 ms typically at 2 to 0 x V
set
-
Critical impulse time
10 ms typically at 0 to 2 x V
set
-
Impulse margin time
15 ms typically
-
Busbar protection REB650
1MRK 505 265-BUS B
Version 1.1 ANSI
32
ABB Power Grids
© Copyright 2011 ABB Power Grids. All rights reserved