Table 53. IEC Inverse time characteristics
Function
Range or value
Accuracy
Operating characteristic:
(
)
=
×
-
æ
ö
ç
÷
ç
÷
è
ø
1
P
A
t
td
I
EQUATION1653 V1 EN-US
I = I
measured
/I
set
td = (0.05-999) in steps of 0.01
-
IEC Normal Inverse
A=0.14, P=0.02
IEC 60255-151, class 5 +
40 ms
IEC Very inverse
A=13.5, P=1.0
IEC Inverse
A=0.14, P=0.02
IEC Extremely inverse
A=80.0, P=2.0
IEC Short time inverse
A=0.05, P=0.04
IEC Long time inverse
A=120, P=1.0
Table 54. RI and RD type inverse time characteristics
Function
Range or value
Accuracy
RI type inverse characteristic
=
×
-
1
0.236
0.339
t
td
I
EQUATION1656 V1 EN-US
I = I
measured
/I
set
td = (0.05-999) in steps of 0.01
IEC 60255-151, class 5 +
40 ms
RD type logarithmic inverse
characteristic
=
-
×
æ
ö
ç
÷
è
ø
5.8
1.35
t
I
In
td
EQUATION1657 V1 EN-US
I = I
measured
/I
set
td = (0.05-999) in steps of 0.01
IEC 60255-151, class 5 +
40 ms
Busbar protection REB650
1MRK 505 265-BUS B
Version 1.1 ANSI
40
ABB Power Grids
© Copyright 2011 ABB Power Grids. All rights reserved