Section 5
Relay physical connections
RER620
77
Application Manual
5.2
Outputs
5.2.1
Outputs for tripping and controlling
Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of
controlling most circuit breakers. They can be used for any such application. However,
recloser closing and opening signals are issued from UPD module as described in section
5.2.4.
Table 18:
Output contacts
5.2.2
Outputs for signaling
Output contacts SO1 and SO2 in slot X100 or SO1, SO2, SO3 and SO4 in slot X105/X110
(optional) can be used for signaling on pickup and tripping of the relay. On delivery from
the factory, the pickup and alarm signals from all the protection stages are routed to
signaling outputs.
Table 19:
Output contacts X100-10…14
Terminal
Description
X100-6
PO1, NO
X100-7
PO1, NO
X100-8
PO2, NO
X100-9
PO2, NO
X100-15
PO3, NO (TCS resistor)
X100-16
PO3, NO
X100-17
PO3, NO
X100-18
PO3 (TCS1 input), NO
X100-19
PO3 (TCS1 input), NO
X100-20
PO4, NO (TCS resistor)
X100-21
PO4, NO
X100-22
PO4, NO
X100-23
PO4 (TCS1 input), NO
X100-24
PO4 (TCS1 input), NO
Terminal
Description
X100-10
SO1, common
X100-11
SO1, NC
X100-12
SO1, NO
X100-13
SO2, COM
X100-14
SO2, NO
Содержание Relion 620 Series
Страница 1: ...Relion 620 series Advanced Recloser Protection and Control RER620 Application Manual...
Страница 2: ......
Страница 16: ...Section 1 1MAC308145 MB E Introduction 10 RER620 Application Manual...
Страница 26: ...Section 2 1MAC308145 MB E RER620 overview 20 RER620 Application Manual...
Страница 86: ...Section 5 1MAC308145 MB E Relay physical connections 80 RER620 Application Manual...
Страница 89: ......