Section 3
1MAC308145-MB E
RER620 application
22
RER620
Application Manual
3.2
Functions
Table 7:
Functions included in the RER620 standard configuration RA01, RA02
Function
IEC61850
IEC60617
ANSI/C37.2
Current Protection
Single-phase non-directional time overcurrent protection with 1-ph trip option, low stage
SPHLPTOC1
3I>(1)
51P
Single-phase non-directional time overcurrent protection with 1-ph trip option, high stage 1
SPHLPTOC2
3I>(2)
50P-1
Single-phase non-directional time overcurrent protection with 1-ph trip option, high stage 2
SPHHPTOC1
3I>>(1)
50P-2
Single-phase non-directional instantaneous overcurrent protection with 1-ph trip option
SPHIPTOC1
3I>>>(1)
50P-3
Non-directional time overcurrent ground-fault protection, low stage
XEFLPTOC2
Io>(2)
51N
Non-directional time overcurrent ground-fault protection, high stage 1
XEFLPTOC3
Io>(3)
50N-1
Non-directional time overcurrent ground-fault protection, high stage 2
XEFHPTOC3
Io>>(3)
50N-2
Non-directional instantaneous time overcurrent ground-fault protection
XEFIPTOC2
Io>>>(2)
50N-3
Non-directional sensitive earth-fault
EFLPTOC3
Io>(3)
50SEF
Negative sequence non-directional time overcurrent protection 1
XNSPTOC1
I2 >(1)
46-1
Negative sequence non-directional time overcurrent protection 2
XNSPTOC2
I2 >(2)
46-2
Phase discontinuity protection
PDNSPTOC1
I2/I1>
46PD
Three-phase inrush detector
INPHAR
3I2f >
INR
Directional Protection
Single-phase directional overcurrent protection, low stage 1
SDPHLPDOC1
3I >->(1)
67/51P-1
Single-phase directional overcurrent protection, low stage 2
SDPHLPDOC2
3I >->(2)
67/51P-2
Directional ground-fault protection, low stage 1
XDEFLPDEF1
Io>->(1)
67/51N-1
Directional ground-fault protection, low stage 2
XDEFLPDEF2
Io>->(2)
67/51N-2
Cold Load Timers
Cold load timer 1 Phase A (in seconds)
TPSGAPC1
TPS(1)
62CLD-1
Cold load timer 2 Phase A (in minutes)
TPMGAPC1
TPM(1)
62CLD-2
Cold load timer 1 Phase B (in seconds)
TPSGAPC2
TPS(2)
62CLD-3
Cold load timer 2 Phase B (in minutes)
TPMGAPC2
TPM(2)
62CLD-4
Cold load timer 1 Phase C (in seconds)
TPSGAPC3
TPS(3)
62CLD-5
Cold load timer 2 Phase C (in minutes)
TPMGAPC3
TPM(3)
62CLD-6
Voltage Protection
Single-phase overvoltage 1, source 1 low stage
SPHPTOV1
3U >(1)
59-1
Single-phase overvoltage 2, source 1 high stage
SPHPTOV2
3U >(2)
59-2
Single-phase overvoltage 3, source 2 low stage
SPHPTOV3
3U >(3)
59-3
Single-phase undervoltage 1, source 1 low stage
SPHPTUV1
3U <(1)
27-1
Single-phase undervoltage 2, source 1 high stage
SPHPTUV2
3U <(2)
27-2
Single-phase undervoltage 3, source 2 low stage
SPHPTUV3
3U <(3)
27-3
Positive sequence overvoltage protection, source1
PSPTOV1
U1>(1)
59PS-1
Positive sequence overvoltage protection, source 2
PSPTOV2
U1>(2)
59PS-2
Negative sequence overvoltage protection, source1
NSPTOV1
U2>(1)
47
Negative sequence overvoltage protection, source 2
NSPTOV2
U2>(2)
47-2
Содержание Relion 620 Series
Страница 1: ...Relion 620 series Advanced Recloser Protection and Control RER620 Application Manual...
Страница 2: ......
Страница 16: ...Section 1 1MAC308145 MB E Introduction 10 RER620 Application Manual...
Страница 26: ...Section 2 1MAC308145 MB E RER620 overview 20 RER620 Application Manual...
Страница 86: ...Section 5 1MAC308145 MB E Relay physical connections 80 RER620 Application Manual...
Страница 89: ......