Section 2
1MAC308145-MB E
RER620 overview
18
RER620
Application Manual
The default passwords can be changed with Administrator user rights.
Table 5:
Predefined user categories
2.6
Communication
The relay supports different communication protocols: IEC 61850, DNP3.0 Level 2,
Modbus, IEC 104 – all using TCP/IP. DNP3, Modbus, IEC 101 also support serial
communication, PG&E 2179 over serial. Operational information and control are
available through these protocols. However, some communication functionality, for
example, horizontal peer-to-peer communication between the relays and parameters
setting, is only enable by the IEC 61850 communication protocol.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter setting and DFR records can be accessed using the IEC
61850 protocol. Oscillographic files are available to any Ethernet-based application in the
standard COMTRADE format. Further, the relay can send and receive binary signals from
other relays (so called horizontal communication) using the IEC61850-8-1 GOOSE
profile, where the highest performance class with a total transmission time of 3 ms is
supported. Further, the relay supports sending and receiving of analog values using
GOOSE messaging. The relay meets the GOOSE performance requirements for tripping
applications in distribution substations, as defined by the IEC 61850 standard. The relay
can simultaneously report events to five different clients on the station bus.
User authorization is disabled by default but WHMI always uses
authorization.
Username
User rights
VIEWER
Read only access
OPERATOR
• Selecting remote or local state with
(only locally)
• Changing setting groups
• Controlling
• Clearing alarm and indication LEDs and textual indications
ENGINEER
• Changing settings
• Clearing event list
• Clearing DFRs
• Changing system settings such as IP address, serial baud rate or
DFR settings
• Setting the relay to test mode
• Selecting language
ADMINISTRATOR
• All listed above
• Changing password
• Factory default activation
For user authorization for PCM600, see PCM600 documentation.
Содержание Relion 620 Series
Страница 1: ...Relion 620 series Advanced Recloser Protection and Control RER620 Application Manual...
Страница 2: ......
Страница 16: ...Section 1 1MAC308145 MB E Introduction 10 RER620 Application Manual...
Страница 26: ...Section 2 1MAC308145 MB E RER620 overview 20 RER620 Application Manual...
Страница 86: ...Section 5 1MAC308145 MB E Relay physical connections 80 RER620 Application Manual...
Страница 89: ......