User authorization is disabled by default and can be enabled via the
LHMI or WHMI
Main Menu/Configuration/Authorization
.
Table 19:
Predefined user categories
Username
LHMI
password
WHMI password User rights
VIEWER
0001
remote0001
Only allowed to view
OPERATOR
0002
remote0002
Authorized to make operations
ENGINEER
0003
remote0003
Allowed to change IED parameters, but no
operation rights
ADMINISTRATOR
0004
remote0004
Full access
For user authorization for PCM600, see PCM600 documentation.
8.4
Using PCM600
8.4.1
Setting the communication between IEDs and PCM600
The communication between the IED and PCM600 is independent of the used
communication protocol within the substation or to the NCC. It can be seen as a
second channel for communication.
The communication media is always Ethernet and the protocol is TCP/IP.
Each IED has an Ethernet front connector for PCM600 access. Depending on the
station concept and the used station protocol, additional Ethernet interfaces may be
available on the rear side of the IED. All Ethernet interfaces can be used to connect
PCM600.
When an Ethernet based station protocol is used, the PCM600 communication can
use the same Ethernet port and IP address. The IED is able to separate the
information belonging to the PCM600 dialog.
To configure the physical connection and the IP addresses:
Section 8
1MRS756708 C
Commissioning
98
615 series
Operation Manual