Some parameters have an edit-copy. If editing is cancelled, the values with an edit-
copy are immediately restored to the original value. The values without an edit-
copy, such as string values, are restored to the original value only after a reboot
even though the edited value is not stored in the flash memory.
1.
Click
Write to IED
after editing parameter values to put the values into IED's
database for use.
A070931 V4 EN
Figure 37:
Writing values to IED
The values are not stored to the flash memory.
2.
Click
Commit
to write the values to the flash memory.
•
Click
Reject
to cancel saving settings.
•
If the parameter has an edit-copy, the original parameter value is
restored.
•
If the parameter does not have an edit-copy, the edited parameter
value remains visible until you reboot the IED. However, the
edited value is not stored in non-volatile memory and thus the
reboot restores the original value.
1MRS756708 C
Section 4
Using the HMI
615 series
53