![background image](http://html1.mh-extra.com/html/abb/relion-615-series/relion-615-series_operation-manual_3364377126.webp)
1.
Select
Main Menu/Tests/Function tests/Current protection/PHLPTOC
and press
.
2.
Select the output signal to be activated or deactivated with
or
and
press
.
3.
To deactivate all output signals for the function, select
Reset
with
or
and press
.
8.6.4
Selecting the internal fault test
The internal fault may be tested by using the LHMI. When enabling the test, the
internal relay fault output contact is activated, the green Ready LED will be
blinking and internal fault test indication is shown on the LHMI. See Technical
Manual for internal relay fault output contact location.
Differing from real internal fault situation, the other output contacts
are not released and locked during the test. In other words,
protection functions can operate and trip the outputs when the
internal fault is tested.
1.
Select
Main menu/Tests/IED test/Internal fault test
and press
.
A071156 V2 EN
Figure 89:
Internal fault test
2.
Select the value with
or
.
3.
Press
to confirm the selection.
8.7
ABB Product Data Registration
The ABB Product Data Registration feature traces composition changes related to
the IED's SW or HW.
Section 8
1MRS756708 C
Commissioning
118
615 series
Operation Manual