See the application manual for product-specific connection diagrams.
5.2.1
Connecting ring-lug type wires
Ring-lug type insulated terminal can be used for signal connector X120. The
maximum outside diameter for the M4 ring-lug type terminals is 9 mm.
5.3
Connecting protective earthing
The earth lead must be at least 6.0 mm
2
. If the length of the earth
lead is long, the cross section of the wire must be increased.
Use fine copper wire as the earth lead.
To connect a separate earth protection lead: