A070588 V4 EN
Figure 20:
IED and the test switch RTXP 18 mounted into a 19" equipment panel
4.3.8
Rack mounting the IED in a combiflex 19" equipment frame
(Type RHGT 19" 4U variant C)
A mounting bracket is needed for rack mounting the IED into a combiflex 19"
equipment frame, a different bracket is in installation with test switch. In addition
to the detailed mounting instructions, the mounting kit includes:
•
Mounting bracket for the case and optionally with RTXP test switch
1.
Install the mounting bracket into the combiflex equipment frame by using
tapping screws ST3.5x13 from rear side.
The type of mounting bracket to be used depends on whether
the IED is installed into the frame on its own or with a test
switch.
2.
Loosen the four M5 fixing screws in the case to fit the case into the mounting
bracket.
3.
Mount the case to the mounting bracket.
4.
Tighten the M5 screws.
The allowed range for the fixing screws’ tightening torque is 0.7...1 Nm.
5.
Install the plug-in unit into the case.
Section 4
1MRS756375 K
Mounting
34
615 series
Installation Manual
Содержание Relion 615 series