When internal voltage selection is needed, the voltage transformer circuit
connections are made according to figure
. The voltage from the busbar 1 VT is
connected to U3PBB1 and the voltage from busbar 2 is connected to U3PBB2. The
voltage from the line VT is connected to U3PLN1. The positions of the
disconnectors and VT fuses shall be connected as shown in figure
. The voltage
selection parameter
CBConfig
is set to
Double bus
.
12.1.4
Setting guidelines
M12550-3 v14
The setting parameters for the Synchronizing, synchrocheck and energizing check
function SESRSYN are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN function via the
LHMI.
Common base IED value for primary voltage ( UBase ) is set in a Global base
value function, GBASVAL, found under
Main menu//Configuration/Power
system/GlobalBaseValue/GBASVAL_X/UBase
. The SESRSYN function has one
setting for the bus reference voltage (
GblBaseSelBus
) and one setting for the line
reference voltage (
GblBaseSelLine
) which independently of each other can be set
to select one of the twelve GBASVAL functions used for reference of base values.
This means that the reference voltage of bus and line can be set to different values.
The settings for the SESRSYN function are found under
Main menu/Settings/IED
Settings/Control/Synchronizing(25,SC/VC)/SESRSYN(25,SC/VC):X
has been
divided into four different setting groups: General, Synchronizing, Synchrocheck
and Energizingcheck.
General settings
Operation
: The operation mode can be set
On
or
Off
. The setting
Off
disables the
whole function.
GblBaseSelBus
and
GblBaseSelLine
These configuration settings are used for selecting one of twelve GBASVAL
functions, which then is used as base value reference voltage, for bus and line
respectively.
SelPhaseBus1
and
SelPhaseBus2
Configuration parameters for selecting the measuring phase of the voltage for
busbar 1 and 2 respectively, which can be a single-phase (phase-neutral), two-
phase (phase-phase) or a positive sequence voltage.
SelPhaseLine1
and
SelPhaseLine2
Configuration parameters for selecting the measuring phase of the voltage for line
1 and 2 respectively, which can be a single-phase (phase-neutral), two-phase
(phase-phase) or a positive sequence voltage.
Section 12
1MRK 505 393-UEN B
Control
224
Line differential protection RED650 2.2 IEC
Application manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 32: ...26 ...
Страница 82: ...76 ...
Страница 112: ...106 ...
Страница 152: ...146 ...
Страница 208: ...202 ...
Страница 214: ...208 ...
Страница 282: ...276 ...
Страница 356: ...350 ...
Страница 404: ...398 ...
Страница 408: ...402 ...
Страница 442: ...436 ...
Страница 452: ...446 ...
Страница 453: ...447 ...