12.1.3.1
Single circuit breaker with single busbar
M12324-3 v12
WA1_MCB
LINE
WA1
QB1
QA1
IEC10000093-4-en.vsd
LINE_VT
LINE_MCB
WA1_MCB
SESRSYN
U3PBB1*
U3PBB2*
U3PLN1*
U3PLN2*
GRP_OFF
UB1OK
UB1FF
ULN1OK
ULN1FF
WA1_VT
WA1_VT
LINE_VT
LINE_MCB
WA1_MCB
IEC10000093 V4 EN-US
Figure 98:
Connection of SESRSYN function block in a single busbar
arrangement
illustrates connection principles for a single busbar. For the SESRSYN
function there is one voltage transformer on each side of the circuit breaker. The
voltage transformer circuit connections are straightforward; no special voltage
selection is necessary.
The voltage from busbar VT is connected to U3PBB1 and the voltage from the line
VT is connected to U3PLN1. The conditions of the VT fuses shall also be
connected as shown above. The voltage selection parameter
CBConfig
is set to
No
voltage sel
.
Section 12
1MRK 505 393-UEN B
Control
222
Line differential protection RED650 2.2 IEC
Application manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 32: ...26 ...
Страница 82: ...76 ...
Страница 112: ...106 ...
Страница 152: ...146 ...
Страница 208: ...202 ...
Страница 214: ...208 ...
Страница 282: ...276 ...
Страница 356: ...350 ...
Страница 404: ...398 ...
Страница 408: ...402 ...
Страница 442: ...436 ...
Страница 452: ...446 ...
Страница 453: ...447 ...