4.2.1
Setting of the phase reference channel
SEMOD55055-5 v3
All phase angles are calculated in relation to a defined reference. An appropriate
analog input channel is selected and used as phase reference. The parameter
PhaseAngleRef
defines the analog channel that is used as phase angle reference.
4.2.1.1
Example
SEMOD55055-11 v5
4.2.2
Setting of current channels
SEMOD55055-16 v6
The direction of a current to the IED is depending on the connection of the CT.
Unless indicated otherwise, the main CTs are supposed to be star connected and
can be connected with the earthing point to the object or from the object. This
information must be set in the IED. The convention of the directionality is defined
as follows: A positive value of current, power, and so on means that the quantity
has the direction into the object and a negative value means direction out from the
object. For directional functions the direction into the object is defined as Forward
and the direction out from the object is defined as Reverse. See Figure
A positive value of current, power, and so on (forward) means that the quantity
flows towards the object. A negative value of current, power, and so on (reverse)
means that the quantity flows away from the object. See Figure
Protected Object
Line, transformer, etc
Forward
Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse
Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
IEC05000456 V1 EN-US
Figure 3:
Internal convention of the directionality in the IED
With correct setting of the primary CT direction,
CTStarPoint
set to
FromObject
or
ToObject
, a positive quantities always flowing towards the protected object and a
direction defined as Forward always is looking towards the protected object. The
following examples show the principle.
4.2.2.1
Example 1
SEMOD55055-23 v6
Two IEDs used for protection of two objects.
Section 4
1MRK 505 393-UEN B
Analog inputs
40
Line differential protection RED650 2.2 IEC
Application manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 32: ...26 ...
Страница 82: ...76 ...
Страница 112: ...106 ...
Страница 152: ...146 ...
Страница 208: ...202 ...
Страница 214: ...208 ...
Страница 282: ...276 ...
Страница 356: ...350 ...
Страница 404: ...398 ...
Страница 408: ...402 ...
Страница 442: ...436 ...
Страница 452: ...446 ...
Страница 453: ...447 ...