Set
Unblock
=
Off
(Set to
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
= 0.035 s
Set
DeltaI
= 10 %IB
Set
DeltaU
= 5 %UB
Set
Delta3I0
= 10 %IB
Set
Delta3U0
= 5 %UB
13.1.3.3
Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
On
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
13.1.3.4
Permissive overreaching scheme
M13869-34 v4
Set
Operation
=
On
Set
Scheme type
=
Permissive OR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
13.1.3.5
Unblocking scheme
M13869-43 v4
Set
Unblock
=
Restart
(Loss of guard signal will give both trip and alarm
Choose
NoRestart if only trip is required)
Set
tSecurity
= 0.035 s
13.1.3.6
Intertrip scheme
M13869-62 v5
Set
Operation
=
On
Set
SchemeType
=
Intertrip
Set
tCoord
= 50 ms (10 ms + maximal transmission time)
Table continues on next page
Section 13
1MRK 505 393-UEN B
Scheme communication
284
Line differential protection RED650 2.2 IEC
Application manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 32: ...26 ...
Страница 82: ...76 ...
Страница 112: ...106 ...
Страница 152: ...146 ...
Страница 208: ...202 ...
Страница 214: ...208 ...
Страница 282: ...276 ...
Страница 356: ...350 ...
Страница 404: ...398 ...
Страница 408: ...402 ...
Страница 442: ...436 ...
Страница 452: ...446 ...
Страница 453: ...447 ...