Section 7
Impedance protection
7.1
Distance protection ZMFPDIS
GUID-CC4F7338-2281-411D-B55A-67BF03F31681 v4
7.1.1
Identification
GUID-8ACD3565-C607-4399-89D2-A05657840E6D v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Distance protection zone
ZMFPDIS
S00346 V1 EN-US
21
7.1.2
Application
IP14961-1 v2
GUID-2F952D87-6BEB-4425-B823-DF8511B9E742 v3
The distance protection function in the IED is designed to meet basic requirements
for application on transmission and sub-transmission lines (solid earthed systems)
although it can also be used on distribution levels.
Sub-transmission networks are being extended and often become more and more
complex, consisting of a high number of multi-circuit and/or multi terminal lines of
very different lengths. These changes in the network will normally impose more
stringent demands on the fault clearing equipment in order to maintain an
unchanged or increased security level of the power system.
7.1.2.1
System earthing
GUID-EB5B5594-AA81-4FC5-BBC0-7627A8609A23 v1
The type of system earthing plays an important role when designing the protection
system. Some hints with respect to distance protection are highlighted below.
Solidly earthed networks
GUID-6B0F02F4-18ED-415E-8D48-0A1648F7CE00 v2
In solidly earthed systems, the transformer neutrals are connected directly to earth
without any impedance between the transformer neutral and earth.
1MRK 505 393-UEN B
Section 7
Impedance protection
Line differential protection RED650 2.2 IEC
107
Application manual
Содержание RED650
Страница 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 32: ...26 ...
Страница 82: ...76 ...
Страница 112: ...106 ...
Страница 152: ...146 ...
Страница 208: ...202 ...
Страница 214: ...208 ...
Страница 282: ...276 ...
Страница 356: ...350 ...
Страница 404: ...398 ...
Страница 408: ...402 ...
Страница 442: ...436 ...
Страница 452: ...446 ...
Страница 453: ...447 ...