Quick start-up guide
19
Quick start-up guide
Overview
This chapter presents the steps to take during the start-up of the
RECA-01 EtherCAT® Adapter module.
WARNING!
Follow the safety instructions given in this manual and
the
Hardware Manual
of the drive.
Mechanical installation
• Insert the RECA-01 into its specified slot in the drive (SLOT2 for
ACS550, SLOT1 for ACS800).
• Fasten the two screws.
Electrical installation
• Connect the Ethernet cable (RJ-45 connector) to the RECA-01
module. Standard CAT 5 UTP or STP cables can be used.
Avoid parallel runs with power (e.g. motor) cables.