Quick start-up guide
21
Example configuration with ACS800 using the DSP 402 profile
Master system configuration
This section guides the user to configure the RECA-01 module in
the EtherCAT® network using Beckhoff's TwinCAT System
Manager. If you are using another master system, consult its
manual for information on configuring the network.
• Select and import the Device Description File for the drive.
EtherCAT® Device Description files are XML files containing
configuration information of the drive. The files can be obtained
from your local ABB representative or from www.abb.com
• Add the drive to the network configuration either manually or by
scanning subdevices (boxes) in the EtherCAT® device (see
figure
Scan Boxes in TwinCAT
on
page 22
).
51.01 MODULE TYPE
ETHERCAT
51.02 TRANSPARENT/
PROFILE MODE
1 (TRANSPARENT, ABB
DRIVES)
98.02 COMM PROT SEL
EXT FBA
Drive parameter
Example setting for ACS800
10.01 EXT1 STRT/STP/DIR
COMM.CW
10.03 REF DIRECTION
REQUEST
11.02 EXT1/EXT2/SELECT
EXT1
11.03 EXT REF1 SELECT
COMM.REF
16.01 RUN ENABLE
YES
16.04 FAULT RESET SEL
COMM.CW
51.01 MODULE TYPE
ETHERCAT
51.02 TRANSPARENT/
PROFILE MODE
0 (DSP 402)
98.02 COMM MODULE LINK
FIELDBUS
98.07 COMM PROFILE
GENERIC
Содержание RECA-01
Страница 1: ...ABB Drives User s Manual EtherCAT Adapter Module RECA 01 ...
Страница 2: ...EtherCAT is registered trademark and patented technology licensed by Beckhoff Automation GmbH Germany ...
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 24: ...Quick start up guide 24 ...
Страница 26: ...Mechanical installation 26 ...
Страница 28: ...Electrical installation 28 ...
Страница 32: ...Master configuration 32 ...
Страница 56: ...Communication 56 ...
Страница 72: ...CoE object dictionary 72 ...
Страница 80: ...CoE Error codes 80 ...
Страница 82: ...Definitions and abbreviations 82 ...