5 - Installation
42
C
haracteristics and sizing of the cable for BACKUP output
Three-pole cable required. The cross-section of the AC line conductor
must be sized in order to prevent unwanted disconnections of the in-
verter from the grid due to high impedance of the line that connects the
inverter to the power supply point.
The table shows the maximum length of the line conductor based on the
cross-section of this conductor:
Conductor cross-section of line
(mm²)
Maximum length of the
line conductor (m)
1.5
6 m
2.5
11 m
4
19 m
The values are calculated in nominal power conditions, considering:
- loss of power along the line no greater than 1%
- use of copper cable, with HEPR rubber insulation and positioned in open air
L
oad protection switch (AC disconnect switch) for BACKUP output
To protect the AC BACKUP connection line of the inverter, a device must
be installed to protect against maximum current and leakage to ground,
with the following characteristics:
REACT2-3.6-TL
REACT2-5.0-TL
Type
Automatic circuit breaker with differen-
tial thermal magnetic protection
Voltage rating
230 Vac
Current rating
32 A
Magnetic protection type
B/C
Type of differential protection
A/AC
Differential sensitivity
30 mA
Number of poles
2
C
onnection to AC BACKUP output terminal block
To avoid
ULVNVRIHOHFWULFDOVKRFNDOOZLULQJRSHUDWLRQVPXVWEHFDUULHGRXWDIWHUWKH
,QYHUWHUVZLWFKRII
Strip 10mm of sheathing from the cables and then insert into the inverter
the cable, making it pass through the AC output (BACKUP) cable gland
16
; the maximum diameter of the cable accepted by the cable gland is
from 10 to 17 mm².
Connect on the AC output (BACKUP) screw terminal block
42
the ground
cable (yellow-green) to protect against contact marked by the symbol , the
neutral cable (usually blue) to the terminal marked by the letter
N
and the
phase cable to the terminal marked by the screen-print
L
; every indivi-
dual terminal of the terminal block accepts a cable with maximum section
RIPPð,WLVQHFHVVDU\WR¿[WKH$&FDEOHVWRWKHWHUPLQDOEORFNZLWKD
tightening torque of at least 1,5 Nm).
2QFHWKHFRQQHFWLRQWRWKHWHUPLQDOEORFNKDVEHHQPDGH¿UPO\VFUHZ
the cable gland (7.5 Nm tightening torque) and check the tightness.
N
L
max 4 mm²
10 ÷ 17 mm