38
EN
—
Technical data table
PVS-166-TL US
PVS-175-TL US
Input side
Absolute maximum DC input voltage
(Vmax,abs)
1500 V
Start-up DC input voltage
(Vstart)
750 V (650…1000 V)
Operating DC input voltage range
(Vdcmin...Vdcmax)
0.7 x Vstart…1500 V (min 600 V)
Rated DC input voltage
(Vdcr)
1100 V
Rated DC input power
(Pdcr)
169 000 W @ 40°C
188 000 W @ 30°C
(177 kW @ 40°C)
Number of independent MPPT
12
MPPT input DC voltage range
(VMPPTmin...VMPPTmax)
at
Pacr
850..1350 V
Maximum DC input current for each MPPT
(IMPPTmax)
22 A
Maximum input short circuit current for each MPPT
(ISCmax)
30 A
Number of DC input pairs for each MPPT
2 DC inputs per MPPT
DC connection type
PV quick fit connector
1)
Input protection
DC Series Arc Fault Circuit Interrupter
Type I acc. to UL 1699B with single-MPPT sensing capability
Reverse polarity protection
Yes, from limited current source
Input over voltage protection for each MPPT - replaceable surge
arrester
Type 2 with monitoring
Photovoltaic array isolation control (Insulation Resistance, R-iso)
Yes (pre start-up R-iso measurement)
Residual Current Monitoring Unit (leakage current protection)
Yes (dynamic GFDI)
DC Load Breaking Disconnect Switch (rating for each MPPT)
30A/1500V ; 50A/1000V
Fuse rating
N/A, No fuses required
String current monitoring
MPPT-level current sense
Output side
AC Grid connection type
Three phase 3W+PE
Rated AC power (P
acr
@cosφ=1)
166 500 W @ 40°C
175 000 W @ 40°C
Maximum AC output power (P
acmax
@cosφ=1)
166 500 W @ 40°C
185 000 W @≤ 30°C
Maximum apparent power
(Smax)
166 500 VA
185 000 VA
Rated AC grid voltage
(Vac,r)
800 V
AC voltage range
552...960
2)
Maximum AC output current
(Iac,max)
134 A
Rated output frequency
(fr)
50 Hz / 60 Hz
Output frequency range
(fmin...fmax)
45…55 Hz / 55…65 Hz
2)
Nominal power factor / adjustable range at Smax
> 0.995
0.75 Lead…0.75 Lag
> 0.995
0.8 Lead…0.8 Lag
Total current harmonic distortion
< 3%
Max DC current injection (% of In)
< 0.5%*In
AC wire range
4x1x2/0 AWG to 4x1x400 kcmil, Cu/Al
3)
AC plate
Opening for Trade size 3 conduit
AC connection type
Copper Busbar for ring terminal lug connections with M10
stud type terminal block (bolts included)
Output protection
Anti-islanding protection
Meets UL1741 / IEEE1547 requirements
Output overvoltage protection - replaceable surge protection de-
vice
Type 2 with monitoring
(Continue to next page)