- 25 -
000959AG
3 - Characteristics
Table: Technical Data
PVS-100-TL
PVS-120-TL
Communication
Embedded communication interfaces
1x RS485, 2x Ethernet (RJ45),
WLAN (IEEE802.11 b/g/n @ 2,4 GHz)
User Interface
4 LEDs, Web User Interface, Mobile APP
Communication protocol
Modbus RTU/TCP (Sunspec compliant)
Commissioning tool
Web User Interface, Mobile APP/APP for plant level
Remote monitoring services
Aurora Vision® monitoring portal
Advanced features Embedded logging, direct telemetry data transferring to ABB cloud
Environmental
Ambient temperature range
-25...+60°C /-13...140°F with derating above 40°C / 104 °F
Storage temperature
-40°C...+85°C / -40°F...185°F
Relative Humidity
4…100 % with condensation
Sound pressure level, typical
68 dB(A) @ 1 m
Maximum operating altitude without derating
2000 m / 6560 ft
Environmental pollution degree
classification for external environments
3
Environmental class
Outdoor
Climatic category according to IEC 60721-3-4
4K4H
Physical
Environmental Protection Rating
IP 66 (IP54 for the cooling section)
Cooling
Forced air
Dimensions (H x W x D) 867x1086x419 mm / 34.2” x 42.8” x 16.5” for -SX, -SY model
867x1086x458 mm / 34.2”x42.8”x18.0” for -SX2, SY2 model
Weight
70kg / 154 lbs for power module ;
~55kg / 121 lbs for Wiring box
Overall max ~125 kg / 276 lbs
Mounting system
Mounting bracket vertical & horizontal support
Overvoltage rating as per IEC 62109-1
II (DC input) III (AC output)
Safety
Safety class
I
Insulation Level
Transformerless
Marking & EMC
CE conformity according to LV and EMC directives
Safety
IEC/EN 62109-1, IEC/EN 62109-2
Grid standard
(check your sales channel for availability)
CEI 0-16, CEI 0-21, IEC 61727, IEC 62116, IEC 60068, IEC
61683, JORDAN IRR-DCC-MV, AS/NZS4777.2, VDE-AR-N
4105, VDE V 0-126-1-1, VFR 2014, Belg C10-C11, UK59/3,
P.O. 12.3, ITC-BT-40,
EN50438 GIreland, CLC-TS 50549-1/2
Accessories
Assembly accessories
- PVS Installation Kit
- AC multicore cable gland plate
(Supports M63 Ø 37…53mm + M25 Ø 10...17mm)
1. Maximum number of opening 5 under overloading
2. Please refer to the document “String inverters – Product manual appendix” available at www.abb.com/solarinverters for informa-
tion on the quick-fit connector brand and model used in the inverter
3. Maximum fuse size supported 20A. Additionally two strings input per MPPT supports 30A fuse size for connecting two strings
per input.
4.
The AC voltage range may vary depending on specific country grid standard
5.
Frequency range may vary depending on specific country grid standard
6. In the event of a fault, limited by the external protection envisaged on the AC circuit
Remark. Features not specifically listed in the present data sheet are not included in the product