![ABB PVS-100-TL Скачать руководство пользователя страница 178](http://html.mh-extra.com/html/abb/pvs-100-tl/pvs-100-tl_product-manual_4142178.webp)
- 178 -
000974AG
8 - Maintenance
R
eplacing the AC surge arrester cartridge (-SX/SX2 models only)
Replacing the AC surge arrester cartridges
22
may be necessary in the
following circumstances:
1. “Alarm” LED flashing, “Power” LED steady ON.
2. Presence of “W019” Error in Inverter Log section of web user interface.
3. The inspection window of AC surge arrester cartridge is RED.
The AC surge arrester cartridges
22
are installed inside the wiring box
02
.
Procedure for replacing one of the AC surge arrester cartridges
22
:
Some inverter parts may be subject to voltages that could be hazardous for the operator.
1.
Before performing any work on the inverter, refer to “Inverter total de-
energization and safe access” chapter on this manual to know all the
necessary step to safely operate on the inverter.
2.
Open the front wiring box cover
07
.
3.
Push the side snaps and pull out the cartridges.
4.
Insert the new cartridge in the empty slot.
22
5.
Close the wiring box front cover
07
.
6.
Re-commission the inverter.