15 ANALOGUE OUTPUTS
15.1 ANALOGUE OUTPUT1
41501
1 = NOT USED; 2 = P SPEED; 3 = SPEED; 4 = FREQUENCY; 5 = CURRENT;
6 = TORQUE; 7 = POWER; 8 = DC BUS VOLT; 9 = OUTPUT VOLT;
10 = APPL OUTPUT; 11 = REFERENCE; 12 = CONTROL DEV;
13 = ACTUAL 1; 14 = ACTUAL 2
15.2 INVERT AO1
41502
0 = NO; Hex FFFF = YES
15.3 MINIMUM AO1
41503
1 = 0 mA; 2 = 4 mA
15.4 FILTER AO1
41504
0 s ... 10 s
1000
10 s
15.5 SCALE AO1
41505
10 % ... 1000 %
10000 1000 %
15.6 ANALOGUE OUTPUT2
41506
1 = NOT USED; 2 = P SPEED; 3 = SPEED; 4 = FREQUENCY; 5 = CURRENT;
6 = TORQUE; 7 = POWER; 8 = DC BUS VOLT; 9 = OUTPUT VOLT;
10 = APPL OUTPUT; 11 = REFERENCE; 12 = CONTROL DEV;
13 = ACTUAL 1; 14 = ACTUAL 2
15.7 INVERT AO2
41507
0 = NO; Hex FFFF = YES
15.8 MINIMUM AO2
41508
1 = 0 mA; 2 = 4 mA
15.9 FILTER AO2
41509
0 s ... 10 s
1000
10 s
15.10 SCALE AO2
41510
10 % ... 1000 %
10000 1000 %
16 SYSTEM CTR INPUTS
16.1 RUN ENABLE
41601
1 = YES; 2 ... 7 = DI1 ... DI6; 8 = COMM.MODULE
16.2 PARAMETER LOCK
41602
0 = OPEN; Hex FFFF = LOCKED
16.3 PASS CODE
41603
0 ... 8 388 607
16.4 FAULT RESET SEL
41604
1 = NOT SEL; 2 ... 7 = DI1 ... DI6; 8 = COMM.MODULE
16.5 USER MACRO IO CHG
41605
1 = NOT SEL; 2 ... 7 = DI1 ... DI6
20 LIMITS
20.1 MINIMUM SPEED
42001
-18000/(number of pole pairs) rpm ...
18000/(number of pole pairs) rpm
1 1 rpm
20.2 MAXIMUM SPEED
42002
20.3 MAXIMUM CURRENT
42003
0 %
I
hd
... 200 %
I
hd
20000 200 %
20.4 MAXIMUM TORQUE
42004
0 % ... 300 %
1
1 %
20.5 OVERVOLTAGE CTRL
42005
0 = OFF; Hex FFFF = ON
20.6 UNDERVOLTAGE CTRL
42006
20.7 MINIMUM FREQ
42007
- 300 Hz ... 300 Hz (effective only when the
SCALAR control mode is selected)
-30000 -300 Hz
20.8 MAXIMUM FREQ
42008
21 START/STOP
21.1 START FUNCTION
42101
1 = AUTO; 2 = DC MAGN; 3 = CNST DC MAGN
21.2 CONST MAGN TIME
42102
30 ms ... 10000 ms
1 1 ms
21.3 STOP FUNCTION
42103
1 = COAST; 2 = RAMP
21.4 DC HOLD
42104
0 = OFF; Hex FFFF = ON
21.5 DC HOLD SPEED
42105
0 rpm ... 3000 rpm
1 1 rpm
21.6 DC HOLD CURR
42106
0 % ... 100 %
1 1 %
Parameter
4xxxx
Register
Alternative Settings
Scaling
0
0 s
100
10 %
0
0 s
100
10 %
0
0 %
300 Hz
30000