![ABB NMBP-01 Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/abb/nmbp-01/nmbp-01_installation-and-startup-manual_2754053.webp)
Appendix B – Parameter Scaling
Installation and Start-up Guide for NMBP-01
B-5
13 ANALOGUE INPUTS
13.1 MINIMUM AI1
41301
1 = 0 mA; 2 = 2 V; 3 = TUNED VALUE; 4 = TUNE
13.2 MAXIMUM AI1
41302
1 = 10 V; 2 = TUNED VALUE; 3 = TUNE
13.3 SCALE AI1
41303
0 ... 100 %
10000 100 %
13.4 FILTER AI1
41304
0 s ... 10 s
1000 10 s
13.5 INVERT AI1
41305
0 = NO; Hex FFFF = YES
13.6 MINIMUM AI2
41306
1 = 0 mA; 2 = 4 mA; 3 = TUNED VALUE; 4 = TUNE
13.7 MAXIMUM AI2
41307
1 = 20 mA; 2 = TUNED VALUE; 3 = TUNE
13.8 SCALE AI2
41308
0 ... 100 %
10000
100 %
13.9 FILTER AI2
41309
0 s ... 10 s
1000 10 s
13.10 INVERT AI2
41310
0 = NO; Hex FFFF = YES
13.11 MINIMUM AI3
41311
1 = 0 mA; 2 = 4 mA; 3 = TUNED VALUE; 4 = TUNE
13.12 MAXIMUM AI3
41312
1 = 20 mA; 2 = TUNED VALUE; 3 = TUNE
13.13 SCALE AI3
41313
0 ... 100 %
10000 100 %
13.14 FILTER AI3
41314
0 s ... 10 s
1000 10 s
13.15 INVERT AI3
41315
0 = NO; Hex FFFF = YES
14 RELAY OUTPUTS
14.1 RELAY RO1 OUTPUT
41401
1 = NOT USED; 2 = READY; 3 = RUNNING; 4 = FAULT; 5 = FAULT(-1);
6 = FAULT(RST); 7 = STALL WARN; 8 = STALL FLT; 9 = MOT TEMP WRN;
10 = MOT TEMP FLT; 11 = ACS TEMP WRN; 12 = ACS TEMP FLT;
13 = FAULT/WARN; 14 = WARNING; 15 = REVERSED; 16 = EXT CTRL;
17 = REF 2 SEL; 18 = CONST SPEED; 19 = DC OVERVOLT;
20 = DC UNDERVOL; 21 = SPEED 1 LIM; 22 = SPEED 2 LIM;
23 = CURRENT LIM; 24 = REF 1 LIM; 25 = REF 2 LIM; 26 = TORQUE 1 LIM;
27 = TORQUE 2 LIM; 28 = STARTED; 29 = LOSS OF REF; 30 = AT SPEED;
31 = ACT 1 LIM; 32 = ACT 2 LIM
14.2 RELAY RO2 OUTPUT
41402
14.3 RELAY RO3 OUTPUT
41403
Parameter
4xxxx
Register
Alternative Settings
Scaling
0
0 %
0
0 s
0
0 %
0
0 s
0
0 %
0
0 s
Содержание NMBP-01
Страница 1: ...ACS 600 Installation and Start up Guide Modbus Plus Adapter Module NMBP 01 ...
Страница 2: ......
Страница 4: ...ii Installation and Start up Guide for NMBP 01 ...
Страница 66: ......