![ABB NMBP-01 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/abb/nmbp-01/nmbp-01_installation-and-startup-manual_2754020.webp)
Chapter 4 – Electrical Installation
4-4
Installation and Start-up Guide for NMBP-01
Fibre Link
The fibre link is used for electrically isolating the option modules from the
high power components. Handle the optic cables with care. For ratings of the
optic cables ABB is supplying with the drives, see Table 4-1 below.
Table 4-1 Fibre Optic Cable Ratings.
The fibre link must be connected between the drive NAMC-01 board and the
NMBP-01 Module. Two fibres are needed to connect the Modbus Plus mod-
ule to the drive. See Figure 4-4 below for correct connection.
Figure 4-4 NAMC Board Fibre Connection.
Parameter
Minimum
Maximum
Unit
Storage Temperature
-55 (-67)
+85 (185)
° C (° F)
Installation Temperature
-20 (-4)
+70 (158)
° C (° F)
Short Term Tensile Force
50
N
Short Term Bend Radius
25 (
31
/
32
” )
mm (in)
Long Term Bend Radius
35 (1
3
/
8
” )
mm (in)
Long Term Tensile Load
1
N
Flexing
1000
cycles