Installation and Start-up Guide for NMBP-01
5-7
11.3 EXT REF1 SELECT
Defines the source for External Reference 1.
KEYPAD, … , DI5U,6D
See the ACS 600 Programming Manual.
COMM MODULE
External Reference 1 comes through the communication module, and is also
data set 2. This Reference value can be received either by using Global Data,
or by performing a register write to address 40111.
11.6 EXT REF2 SELECT
Defines the source for the External Reference 2.
KEYPAD, … , DI5U,6D
See the ACS 600 Programming Manual.
COMM MODULE
External Reference 2 comes through the communication module, and is also
data set 3. This Reference value can be received either by using Global Data,
or by performing a register write to address 40112.
16.1 RUN ENABLE
Defines the source for the Run enable signal to the drive.
YES
The drive is enabled all the time.
DI1, …, DI6
The Run enable signal is connected to the selected digital input.
COMM. MODULE
The Run enable signal comes through the communication module. Bit 1 is for
this purpose in the drive Control Word.
16.4 FAULT RESET SEL
Defines the source for resetting the drive after a fault.
NOT SEL
Faults can be cleared only from the local control panel.
DI1, … , DI6
Faults can be cleared by digital I/O signal.
COMM MODULE
Faults can be cleared using bit 8 of the Control Word. The rising edge of this
bit will clear the fault. This data is received using data set number 1, the Con-
trol Word.
The Control Word can be received either by using Global Data, or by per-
forming a register write to address 4xxxx.