![ABB NMBP-01 Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/abb/nmbp-01/nmbp-01_installation-and-startup-manual_2754050.webp)
Appendix B – Parameter Scaling
B-2
Installation and Start-up Guide for NMBP-01
ANALOGUE OUTPUT SELECTIONS for data sets 5 and 6
Analogue Output
Short name
Description
Scaling
PROCESS SPEED
P SPEED
Process speed
-20000 -100 %
of the value defined with
Parameter 20.1 or 20.2 (DTC Control
Mode) or Parameter 20.7 or 20.8
(SCALAR Control Mode)
SPEED SPEED
Motor
speed
FREQUENCY
FREQ
ACS 600 output frequency
-100 -1 Hz
CURRENT CURRENT
Motor
current
10000 100 %
of motor nominal current
TORQUE
TORQUE
Motor torque
-10000 -100 %
of motor nominal torque
POWER
POWER
Motor power
10000 100 %
of motor nominal power
DC BUS VOLTAGE V
DC BUS V
DC bus voltage of ACS 600
10000 100 %
of nominal DC bus voltage
(560 V d.c. for 380 to 415 V a.c. units;
675 V d.c. for 380 to 500 V a.c. units)
OUTPUT VOLTAGE
OUT VOLT
Calculated motor voltage
10000 100 %
of motor nominal voltage
EXTERNAL REF 2
EXT REF2
External reference 2
10000 100 %
of motor max. speed / nominal torque /
max. process reference (selected with
Parameter 11.6)
APPL BLOCK OUTPUT
APPL OUT
Output of the PID controller (if the
PID Macro is selected), External
reference 2 (External control active),
or Keypad reference 2 (Local control
active)
10000 100 %
ACTUAL VALUE 1
ACT VAL1
PID controller Actual value 1
Available only if the PID Macro is
selected
ACTUAL VALUE 2
ACT VAL2
PID controller Actual value 2
Available only if the PID Macro is
selected
CONTROL DEVIATION
CONT DEV
The difference between the PID
controller reference and the PID
controller actual signal. Available
only if the PID Macro is selected
10000 100 %
100 %
20000
1 Hz
100
0
0 %
100 %
10000
0
0 %
0
0 %
0
0 %
0
0 %
0
0 %
0
-100 %