![ABB MicroFlex e150 Скачать руководство пользователя страница 54](http://html.mh-extra.com/html/abb/microflex-e150/microflex-e150_user-manual_2741054.webp)
54 Electrical installation: AC input, motor and brake
Continuation of motor power cable shielding
When using a motor contactor, or extending the motor cable through a terminal box,
ensure that the motor cable shielding is continued all the way to the motor.
1. Make a single circular cut
in the cable’s outer
sheath, ensuring that the
cable’s braided shield is
not damaged.
2. Slide the section of outer
sheath towards the end of
the cable to expose an
area of braided shield.
Carefully remove the
excess sheath at the end
of the cable.
from
MicroFlex e150
On painted
panels, remove
paint to expose
bare metal.
Optional Motor Cable Management Bracket
OPT-CM-001 (recommended)
from
MicroFlex e150
Metal P-clip
M-Contactor
Terminal box
Motor
from
MicroFlex e150
Содержание MicroFlex e150