46 Electrical installation: AC input, motor and brake
When using unearthed/ungrounded distribution systems, an isolation transformer
with an earthed/grounded secondary is recommended. This provides three-phase AC
power that is symmetrical with respect to earth/ground and can prevent equipment
damage.
Protection class
User protection has been achieved using Protective Class I (EN 61800-5-1), which
requires an earth connection to the unit whenever hazardous voltages are applied.
The equipment provides protection against electric shock by:
• Means of connection of protective earth to accessible live conductive parts.
• Basic insulation.
Earth leakage
Maximum earth leakage from the MicroFlex e150 is 3.4 mA per phase (230 V, 50 Hz
supply). This value does not include the earth leakage from the AC power filter, which
could be much larger (see
EMC filters
on page
166
). If the MicroFlex e150 and filter
are mounted in an enclosure, it is recommended the enclosure is earthed using a
10 mm
2
conductor.
Содержание MicroFlex e150
Страница 1: ...ABB motion control User s manual MicroFlex e150 servo drive MN1961WEN ...
Страница 4: ......
Страница 20: ...20 Introduction to the manual ...
Страница 26: ...26 Hardware description ...
Страница 32: ...32 Mechanical installation ...
Страница 42: ...42 Planning the electrical installation ...
Страница 116: ...116 Start up ...
Страница 126: ...126 Fault tracing ...
Страница 152: ...152 Technical data EtherCAT Conformance Test Certificate ...
Страница 162: ...162 Technical data ...
Страница 178: ...178 Appendix Safe Torque Off STO STO function TüV certificate ...