12
M4M 30
NETWORK ANALYZER USER MANUAL
Climatic conditions
Operating temperature
-25 to 70 °C (K70 acc. to IEC 61557-12)
Storage temperature
-40 to 85 °C (K70 acc. to IEC 61557-12)
Relative humidity
Max 93% (non-condensing) at 40°C
Pollution degree
2
Altitude
< 2000 m
User Interface
Access to device
Touchscreen
Display type
Graphic color display
Display dimensions
70 x 52 mm (3.5")
Communication protocol
Modbus RTU
M4M 30 Modbus, M4M 30 I/O, M4M 30 Rogowski
Communication interface
RS485 with optical isolation
Baud rate
9.6, 19.2, 38.4, 57.6, 115.2 kbps
Parity number
Odd, Even, None
Stop bit
1, 2
Address
1-247
Connector
3 pole terminal
Profibus DP-V0
M4M 30 Profibus
Protocol
Profibus with slave DP-V0 function in
compliance with IEC 61158 regulations
Communication interface
RS485 with optical isolation
Baud rate
Automatic detection [9.6 - 12 Mbps]
Address
0-126
Connector
DB 9 female connector (do not use connectors
with 90° cable outlet)
LED indicators
Green for communication status
Red for communication error
Modbus TCP/IP
M4M 30 Ethernet
Protocol
Modbus TCP/IP
Communication interface
RJ45 (2 ports for daisy-chain feature)
BACnet
M4M 30 Bacnet
Protocol
BACnet/IP
Communication interface
RJ45
Bluetooth
Type
BLE (Bluetooth Low Energy)
Real-time clock
Clock drift
~ 0.4 seconds per day
Battery backup time
~ 3 years without control power
Standards
Power metering and monitoring devices (PMD)
IEC 61557-12 (IEC 62053-22, IEC 62053-23)
Electrical safety
IEC 61010-1
EMC
IEC 61326-1 (IEC 61000-3-2, IEC 61000-3-3, IEC
61000-4-2, IEC 61000-4-3, IEC 61000-4-
4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8,
IEC 61000-4-11)
Содержание M4M 30
Страница 1: ...M4M 30 User manual 2CSG445042D0201 Network Analyzer M4M 30 User manual ...
Страница 2: ......
Страница 13: ...M4M 30 NETWORK ANALYZER USER MANUAL 13 4 Installation 4 1 Assembly 4 2 Disassembly 1 2 3 4 1 2 ...
Страница 82: ... ...
Страница 83: ......
Страница 84: ...ABB S p A Electrification business Viale dell Industria 18 20010 Vittuone MI Italy new abb com low voltage ...