56
M4M 30
NETWORK ANALYZER USER MANUAL
PROFIBUS (M4M 30 Profibus product version)
This section is available on M4M 30 Profibus with Profibus DP-V0 embedded communication.
→
→ Communication → Profibus
Menu
Description
Address
From 1 to 126
If DHCP is disabled, the values of above configurations (IP address, subnet mask, gateway, TCP port) are
the default ones. In this case, it is possible to modify each of above configurations.
If DHCP is enabled, it is not needed to enter the above configurations as they are automatically set.
See Profibus communication manual for details on Profibus communication protocol and communication
map.
BACNET (M4M 30 Bacnet product version)
This section is available on M4M 30 Bacnet with BACnet/IP embedded communication.
→
→ Communication → BACnet
Parameter
Range
Default value
Comments
DHCP
enabled/disabled
disabled
IP address
0.0.0.0-
255.255.255.255
192.168.1.12
This address must create valid
Network prefix and Host address
with combination of subnet mask,
accordingly to IPv4 subnetting.
Additionally some ranges
according to IANA organization
are excluded from valid
values: (127.0.0.0-127.0.0.255),
(224.0.0.0-239.255.255.255) and
255.255.255.255.
Subnet mask
128.0.0.0-
255.255.255.254
255.255.255.0
It must be valid according to IPv4
subnetting.
Gateway
0.0.0.0-
255.255.255.255
192.168.1.1
This address follows the same
restrictions as IP address of device.
UDP port
0-65535
47808
Device instance
0-4194302
228
This ID must be unique across
BACnet network.
BBMD
enabled/disabled
disabled
BBMD IP address
0.0.0.0-
255.255.255.255
0.0.0.0
BBMD UDP port
0-65535
47808
BBMD TTL
0-65535
0
Ekip Connect mode
enabled/disabled
disabled
Ekip Connect mode item shall be used only for FW upgrade via Ekip Connect desktop. When Ekip Connect
mode is enabled, the device reboots and waits for FW upgrade. At the end of the firmware upgrade
operation the device will reboot with the updated firmware. Once the device has rebooted, ensure that
Ekip connect mode parameter is disabled.
If DHCP is disabled, the values of above configurations are the default ones. In this case, it is possible to
modify each of above configurations.
If DHCP is enabled, it is not needed to enter the above configurations as they are automatically set.
See BACnet communication manual for details on BACnet communication protocol and communication map.
Содержание M4M 30
Страница 1: ...M4M 30 User manual 2CSG445042D0201 Network Analyzer M4M 30 User manual ...
Страница 2: ......
Страница 13: ...M4M 30 NETWORK ANALYZER USER MANUAL 13 4 Installation 4 1 Assembly 4 2 Disassembly 1 2 3 4 1 2 ...
Страница 82: ... ...
Страница 83: ......
Страница 84: ...ABB S p A Electrification business Viale dell Industria 18 20010 Vittuone MI Italy new abb com low voltage ...