M4M 30
NETWORK ANALYZER USER MANUAL
11
I/O
Digital Output
Voltage (min - max)
5 - 240 VAC/DC
Current (min - max)
2 - 100 mA
Max ON state drop voltage
1,5 V
Max R value at Min voltage conditions (5 V)
1750 Ohm
Min R value at Max voltage conditions (240 V)
2400 Ohm
Pulse duration
[ms]
20 ms ON, 20 ms OFF
Pulse frequency
25 Hz
Alarm activation delay
[s]
1 - 900 s (programmable)
Alarm return hysteresis
0 - 40% (programmable)
Digital Input
Maximum Voltage
240 VAC/DC
Max voltage for OFF state on input
20 VAC/DC
Min voltage for ON state on input
45 VAC/DC
Analogue Output
Programmable electrical parameters
Span [0 - 20 mA or 4 - 20 mA]
Load
Typical 250 Ohm, max 500 Ohm
Mechanical characteristics
Overall dimensions
96 mm x 96 mm x 77,5 mm
(Depth inside the switchboard: 57mm )
IP degree of protection (IEC 60529)
Front: IP54
Terminals: IP20
Weight
[g]
400
Terminal characteristics
Voltage inputs
Nominal cross section: 2,5 mm
2
Solid/stranded wire: 0,2 - 2,5 mm
2
(AWG 24 - 12)
Pitch: 7,62 mm
Poles: 4
Current inputs
Nominal cross section: 2,5 mm
2
Solid/stranded wire: 0,2 - 2,5 mm
2
(AWG 24 - 12)
Pitch: 5,08 mm
Poles: 8
Screw flanges for fixing
RS-485 Serial port
Nominal cross section: 2,5 mm
2
Solid/stranded wire: 0,2 - 2,5 mm
2
(AWG 24 - 12)
Pitch: 5,08 mm
Poles: 3
I/O
Nominal cross section: 2,5 mm
2
Solid/stranded wire: 0,2 - 2,5 mm
2
(AWG 24 - 12)
Pitch: 5,08 mm
Poles: 5 (Programmable I/O)
Poles: 3 (Programmable I/O only on M4M 30
I/O)
Poles: 3 (Analogue outputs, only on M4M 30 I/O)
Rogowski current probes
Only with ABB Rogowski probes:
-R4M-200: 200 mm diameter (2CSG202150R1101)
-R4M-80: 80 mm diameter (2CSG202160R1101)
Содержание M4M 30
Страница 1: ...M4M 30 User manual 2CSG445042D0201 Network Analyzer M4M 30 User manual ...
Страница 2: ......
Страница 13: ...M4M 30 NETWORK ANALYZER USER MANUAL 13 4 Installation 4 1 Assembly 4 2 Disassembly 1 2 3 4 1 2 ...
Страница 82: ... ...
Страница 83: ......
Страница 84: ...ABB S p A Electrification business Viale dell Industria 18 20010 Vittuone MI Italy new abb com low voltage ...