Configuring the instrument
53
Setting a blocking distance
The blocking distance is the distance
where you do not want the instrument to take measurements
because you know that these measurements will include erroneous or useless data (e.g., right at the
junction between a nozzle and the inside of the vessel, where a giant pulse usually forms.)
To set a blocking distance:
1
Select
Device Setup
>
Safety Setting
>
Blocking distance
.
2
Press
Edit
.
3
Set the necessary blocking distance and press
OK
.
—
Figure 40
Blocking and safety distances
Sensor reference
point
Nozzle length
Blocking distance
Safety distance
Setting a safety distance
The safety distance is a specific distance
where you can take measurements,
at levels preceding the
blocking distance, in case you might want to be informed when such levels are reached.
To set a safety distance:
1
Select
Device Setup
>
Safety Setting
>
Safety distance
.
2
Press
Edit
.
3
Set the necessary safety distance and press
OK
.
Activating a safety distance related alarm
You can raise an alarm when the safety distance threshold is reached.
To to so:
1
Select
Device Setup
>
Safety Setting
>
Safety Dist. Reaction
.
2
Press
Edit
.
3
Highlight
Alarm
and press
OK
.
Содержание LWT300 series
Страница 1: ... USER GUIDE LWT300 series Guided wave radar level transmitter Modbus ...
Страница 36: ...Page intentionally left blank ...
Страница 40: ...Page intentionally left blank ...
Страница 66: ...Page intentionally left blank ...
Страница 70: ...Page intentionally left blank ...
Страница 76: ...Page intentionally left blank ...
Страница 96: ...Page intentionally left blank ...
Страница 98: ...Page intentionally left blank ...
Страница 104: ...Page intentionally left blank ...
Страница 105: ...Page intentionally left blank ...
Страница 106: ...Page intentionally left blank ...
Страница 107: ......