46
Configuring the sensor
Certain sensor parameters can be configured to improve measurement accuracy and reliability. This
configuration can be performed from the
Sensor Setup
menu found under the
Device Setup
menu.
Selecting the application category
The application category is the type of media in which the sensor will be used. Applications are based
on the dielectric constant (DC) value of the medium measured. The default application category
depends on the instrument ordered.
To set the application category:
1
Select
Device Setup
>
Sensor Setup
>
Application Category
.
2
Press
Edit
.
3
Highlight the appropriate application (based on medium measured [DC or liquid vs solid] or the
need to measure the interface between two liquids) and press
OK
.
The
interface application
is used to measure the height in a vessel where substances
with differing dielectric constants separate naturally, as illustrated below. All measures are
performed from the empty/zero value.
Oil
Water
Measured
interface
Measured
level
Содержание LWT300 series
Страница 1: ... USER GUIDE LWT300 series Guided wave radar level transmitter Modbus ...
Страница 36: ...Page intentionally left blank ...
Страница 40: ...Page intentionally left blank ...
Страница 66: ...Page intentionally left blank ...
Страница 70: ...Page intentionally left blank ...
Страница 76: ...Page intentionally left blank ...
Страница 96: ...Page intentionally left blank ...
Страница 98: ...Page intentionally left blank ...
Страница 104: ...Page intentionally left blank ...
Страница 105: ...Page intentionally left blank ...
Страница 106: ...Page intentionally left blank ...
Страница 107: ......