![ABB Integritas Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/abb/integritas/integritas_quick-start-manual_4116003008.webp)
QUICK START GUIDE
Page 8
Version 6.0
© 2021 ABB. All rights reserved.
Step 4A Single Phase
-
Connect 120/240 Single Phase AC Input Section
(Continued)
1.
Verify the charger AC breaker (AC1) is OFF.
2.
Verify AC voltage matches AC Input per
charger label with a meter.
3.
Bring AC wires into the AC Input Box in
conduit through one of the
2”
knockouts
4.
Connect Ground wire (green /green
-
yellow) to lug.
a.
Strip
1/2”
(13mm)
b.
Insert into ground lug.
c.
Tighten lug screw securely.
d.
Pull wire to verify.
5.
Connect each AC wire to the
terminal block in the AC Input Box.
AC terminal connections are labeled at
each position
-
Gnd, L, N, L1, and L2.
a.
Strip
1/4”
(10mm).
b.
Insert into terminal block.
c.
Torque screw to 13 in
-
lb (1.5
Nm).
d.
Pull wire to verify.
Go to Step 5
Gnd
N
L1
Gnd
L2
L1
Gnd
240V
120V
Gnd
L