![ABB Integritas Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/abb/integritas/integritas_quick-start-manual_4116003026.webp)
QUICK START GUIDE
Page 26
Version 6.0
© 2021 ABB. All rights reserved.
Specifications and Application
•
External Surge Protective Device (SPD) is required on all AC inputs.
•
Equipment Safety is Approved in UL1449/IEC 60664
-
1 Installation Category II environments for ambient
temperature up to 50°C.
Models using IP020ACR125ATEZ rectifiers: For input voltages above 266V, the maximum output current and
power are de
-
rated by 2.8% per °C for operating ambient above 40°C.
•
Equipment and subassembly ports:
1. are suitable for connection to intra
-
building or unexposed wiring or cabling;
2. can be connected to shielded intra
-
building cabling grounded at both ends.
•
Grounding / Bonding Network –
Connect to an Isolated Ground Plane (Isolated Bonding Network) or an
Integrated Ground Plane (Mesh
-
Bonding Network or Common Bonding Network).
•
Installation Environment
-
Install where NEC applies.
Reference Documents
These documents are available at
https://abbpowerconversion.com
Document
Title
8600092588P
Pulsar XL Product Manual
850049786
Pulsar Plus Controller Family Troubleshooting
0001258890
Integritas Industrial Battery Chargers Ordering Guide