Precautions
•
Install, service, and operate equipment only by professional, skilled and qualified personnel who have the necessary
knowledge and practical experience with electrical equipment and who understand the hazards that can arise when working
on this type of equipment.
•
Disconnect batteries from outputs and/or follow safety procedures while working on equipment. Batteries may be
connected in parallel with the output of the rectifiers. Turning off the rectifiers will not necessarily remove power from the
bus.
•
Batteries may produce explosive gas. Do not create arcs, smoke, or use an open flame in the vicinity.
•
Do not disconnect permanent bonding connections unless all power inputs are disconnected.
•
Verify that equipment is properly safety earth grounded before connecting power. High leakage currents may be possible.
•
Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy and voltages
are present in the unit and on the interface cables and connectors that can shock or cause serious injury.
•
Use safe lifting practices. The equipment is heavy. Lifting devices are recommended.
•
Use the following precautions in addition to proper job training and safety procedures:
•
Use only properly insulated tools.
•
Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).
•
Follow Lock Out Tag Out (LOTO) procedures: customer specified, site specific, or general as appropriate.
Disconnect all power input before servicing the equipment. Check for multiple power inputs.
•
Wear safety glasses.
•
Follow Personal Protective Equipment requirements: customer specified, site specific, or general as appropriate.
•
Test circuits before touching.
•
Be aware of potential hazards before servicing equipment.
•
Identify exposed hazardous electrical potentials on connectors, wiring, etc.
•
Avoid contacting circuits when removing or replacing covers;.
•
Use a personal ESD strap when accessing or removing electronic components.
•
Follow all warning and precautionary battery instructions, including proper replacement and disposal procedures, to
minimize risk of injury. External batteries, if applicable, are to be installed in accordance with all national and local rules and
regulations, including CEC, part 1.
•
Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including
batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as
pacemakers. Effects decrease with distance.
Important Safety Instructions
1.
SAVE THESE INSTRUCTIONS –
This document contains important safety and operating instructions for the Integritas
battery charger.
2.
Before using battery charger, read all instructions and cautionary markings on battery charger, battery, and all connected
equipment.
3.
Rules and Regulations
-
Follow all national and local rules and regulations when making field connections.
4.
Field
-
wired Conductors
-
Follow all National Electric Code (NEC) and local rules and regulations.
a.
Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
b.
Size AC field
-
wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker
rating.
c.
Size DC field
-
wired conductors with 90°C ampacity (NEC) equal to or greater than circuit breaker/fuse rating.
5.
AC and DC input disconnect/protection
-
Provide accessible devices to remove input power in an emergency.
6.
Compression Connectors
a.
U. S. or Canada installations
-
use Listed/Certified compression connectors to terminate Listed/Certified field
-
wire
conductors.
b.
All installations
-
apply the appropriate connector to the correct size conductor as specified by the connector
manufacturer, using only the connector manufacturer
’
s recommended or approved tooling for that connector.
7.
Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
8.
Cable Dress
-
dress to avoid damage to the conductors and undue stress on the connectors.
9.
Alarm Signals
-
Provide external current limiting protection. Rating—
60
V (125V for 125V charger), 0.5A unless otherwise
noted.
10.
Grounding
-
Connect the equipment chassis directly to ground.
11.
WARNING: Equipment does not provide battery discharge control and protection. To be provided by external battery
source.
12.
WARNING: A battery can present a risk of electrical shock, burn from high short circuit current, fire or explosion from
vented gases. Observe proper precautions.