Pulsar XL Alarm Inputs
Connector
Description—Signal on Pin 1
Pin 2
TB11 (IN007)
“
Dry
”
No Voltage Binary contact input (default is AUX1
“
Air Conditioner Fail
”)
No Voltage Return
TB12 (IN008)
“
Dry
”
No Voltage Binary contact input (default is AUX2
“
Door Open
”)
No Voltage Return
TB13 (IN009)
“
Dry
”
No Voltage Binary contact input (default AUX3
“
High External Ambient
”)
No Voltage Return
TB14 (IN010)
“
Dry
”
No Voltage Binary contact input (default AUX4
“
Low External Ambient
”)
No Voltage Return
TB15 (IN006)
“
Dry
”
No Voltage Binary contact input (default
“
Plant Battery Test (PBT)
”)
No Voltage Return
TB16 (IN005)
“
Dry
”
No Voltage Binary contact input (default
“
Remote Rectifier Standby/Emergency Power Off
”)
No Voltage Return
TB17 (IN001)
“
Dry
”
24V Biased Binary contact input 24V Source (default
“
AUX9 Auxiliary
9”)
24V Source
TB18 (IN002)
“
Dry
”
24V Biased Binary contact input (default AUX8,
“
Auxiliary
8”)
24V Source
TB19 (IN004)
“
Dry
”
24V Biased Binary contact input 24V Source (default OSA1,
“
Open String
”)
24V Source
TB20 (IN003)
“
Dry
”
24V Biased Binary contact input (default AUX6,
“
Hydrogen Present
”)
24V Source
TB21
+24V Alternative external 24VDC back bias input for controller.
+24V DC Return
Pulsar XL System Communications Ports
Connector
Description—Signal on Pin 1
Pin 2
RECT DATA
Connection to isolated rectifier RS485 Galaxy protocol serial bus.
not applicable
1
-
WIRE DATA
Connection to 1
-
Wire temperature probes. 1
-
Wire signal on pin 1.
1
-
Wire Return
Nebula Alarm Outputs
Connector
Description—Signal on Pin 1
Pin 2
TB1
Power Critical Alarm
Common
TB2
Power Major Alarm
Common
TB3
Power Minor Alarm
Common
TB4
Alarm R1 (default is RFA/MRFA)
Common
TB5
Alarm R2 (default is ACFMACF)
Common
TB6
Alarm R3 (default is BD/VLV)
Common
TB7
Alarm R4 (default is GFI)
Common
TB8
Alarm R5 (default is HVSD/HV)
Common
TB9
Alarm R6 (default is multiple rectifier fail MRFA/MFA)
Common
TB10
Alarm R7 (default is
“
Check Battery
”)
Common
Nebula Alarm Inputs
Connector
Description—Signal on Pin 1
Pin 2
TB11 (IN007)
“
Dry
”
No Voltage Binary contact input (default is AUX1
“
Air Conditioner Fail
”)
No Voltage Return
TB12 (IN008)
“
Dry
”
No Voltage Binary contact input (default is AUX2
“
Door Open
”)
No Voltage Return
TB13 (IN009)
“
Dry
”
No Voltage Binary contact input (default AUX3
“
High External Ambient
”)
No Voltage Return
TB14 (IN010)
“
Dry
”
No Voltage Binary contact input (default AUX4
“
Low External Ambient
”)
No Voltage Return
TB15 (IN006)
“
Dry
”
No Voltage Binary contact input (default
“
Plant Battery Test (PBT)
”)
No Voltage Return
TB16 (IN005)
“
Dry
”
No Voltage Binary contact input (default
“
Remote Rectifier Standby/Emergency Power Off
”)
No Voltage Return
TB17 (IN001)
“
Dry
”
24V Biased Binary contact input 24V Source (default
“
AUX9 Auxiliary
9”)
24V Source
TB18 (IN002)
“
Dry
”
24V Biased Binary contact input (default AUX8,
“
Auxiliary
8”)
24V Source
TB19 (IN004)
“
Dry
”
24V Biased Binary contact input 24V Source (default OSA1,
“
Open String
”)
24V Source
TB20 (IN003)
“
Dry
”
24V Biased Binary contact input (default AUX6,
“
Hydrogen Present
”)
24V Source
TB21
+24V Alternative external 24VDC back bias input for controller.
+24V DC Return
Nebula System Communications Ports
Connector
Description—Signal on Pin 1
Pin 2
RECT DATA
Connection to isolated rectifier RS485 Galaxy protocol serial bus.
not applicable
1
-
WIRE DATA
Connection to 1
-
Wire temperature probes. 1
-
Wire signal on pin 1.
1
-
Wire Return